Maintenance Level 1

Level 2

Level 3

Level 4

Level5

Tasks

Recom-

Task Required Task Required Task

Task Required Task

mended

Comp. to be done Comp. to be done Comp.

Required

Comp. to be done Comp.

to be done (Date- 3 months/ (Date-

Semi-

(Date- to be done (Date-

Bi-

(Date-

monthly/ Initials) Break-in Initials) annually/ Initials) Annually/ Initials) annually/ Initials)

10 hrs.

30 hrs.

50 hrs.

100 hrs.

250 hrs.

18. Start and

exercise the unit
at full rated load
(use a load bank
if the site load is
not enough) for
at least 2 hours
looking for leaks,
loose
connections or
components, and
abnormal
operating
conditions.
Correct as
necessary.

19. Perform an

engine oil
analysis (send a
sample to a lab
for results).
Change the
engine oil and
filters if the
analysis results
indicate this is
required.

20. Change the

engine oil.

21. Replace the

engine oil filter(s).

22. Replace engine

spark plugs.
Clean and re-gap
or replace as
necessary.

23. Replace the

engine air
filter(s).

24. Perform a 5

minute no-load
operational run
of the unit
looking for any
post service
problems.

25. Return the unit

to standby setup
for operation
when required.

11-4

Standby Generator Sets

Service Schedule

SrvSchd001 Re

v. A 09/05