beautypg.com

Installation checks and functional tests – Siemens vacuum circuit breaker 38-3AH3 38 kV User Manual

Page 12

background image

Installation checks and
functional tests

The suggested procedure to engage the
racking mechanism is as follows:

1. The circuit breaker must be OPEN. (The

racking shroud cannot be moved if the
circuit breaker is CLOSED.)

2. Hold the socket-end of the crank in one

hand and the crank handle in the other
hand.

3. Place the socket over the end of the

racking-mechanism shaft. Align the
socket with the shoulder on the
racking-mechanism shaft.

Note: If the socket is not aligned, the
socket will not be able to engage the
shoulder of the racking-mechanism shaft.

4. Once alignment is achieved, firmly

push the crank and socket assembly
toward the racking mechanism.

5. When properly engaged, the crank

should remain connected to the
racking mechanism. If the crank does
not remain in position, adjust the
spring plungers clockwise one-half
turn. This will increase the contact
pressure of the spring plunger.

6. To remove the crank, pull the assembly

off of the racking-mechanism shaft.

Note: If the effort to rack the circuit
breaker increases considerably during
racking, or if turning of the racking crank
requires excessive force, stop racking
immediately. Do not try to force the
racking crank to rotate, or parts of the
circuit breaker or racking mechanism could
be damaged. Determine the source of the
problem and correct it before continuing
with racking.

Physical inspections

1. Verify the rating of the circuit breaker is

compatible with both the system and
the switchgear.

2. Perform a visual-damage check. Clean

the circuit breaker of all dust, dirt and
foreign material.

Manual-spring charging check

1. Insert the manual-spring charging

crank into the manual-charge handle
socket as shown in Figure 4. Turn the
crank clockwise (about 48 revolutions)
until the spring condition indicator
shows the closing spring is CHARGED.

2. Repeat the spring discharge check.

3. Verify the springs are DISCHARGED and

the circuit-breaker primary contacts are
OPEN by indicator positions.

As-found and vacuum-integrity check
tests

Perform and record the results of both the
as-found insulation test and the vacuum-
integrity check (dielectric) test. Procedures
for these tests are described in the
Maintenance section of this instruction
manual pages 40-52.

Automatic spring-charging check

Refer to the specific wiring information
and rating label for your circuit breaker to
determine the voltage required and where
the control-voltage signal should be
applied. Usually, spring-charging power is
connected to secondary-disconnect fingers
SD16 and SD15, closing control power to
SD13 and SD15 and tripping power to SD1
and SD2.

When control power is connected to the
type 38-3AH3 vacuum circuit breaker, the
closing springs should automatically
charge, if the racking crank is not engaged.

Figure 4: Manual charging of the

closing springs

12