beautypg.com

Mounting/installation (continued ), Layout of the input block, Position of end plate – Sierra Monitor Corporation EX250-SEN1 User Manual

Page 6

background image

8

9

Mounting/Installation (continued )

Layout of the Input Block

Position the Input Block on the left side of the SI Unit.

Layout of the EX9 series Output Block / Power Block

Position the Output Block / Power Block on the right side of the SI Unit and between
the SI Unit and solenoid valve or End Plate R (on the Output Block side).
1) Output Block for high wattage load

The Output Block for high wattage load cannot be used independently.

Be sure to combine with the Power Block for use.

2) Position of Output Block for high wattage load

The Output Block for high wattage load cannot be mounted at the place nearer to
the SI Unit than the Power Block. However, that place is acceptable if the Power
Block is located between SI Unit and the Output Block for high wattage load.

3) Output Block for low wattage load

The Output Block for low wattage load cannot be mounted at the right side of the
Power Block. Mount to the place nearer to the SI Unit than the Power Block.

Position of End Plate

Be sure to connect the End Plate (on the Input Block side) at the left end of the

manifold.

When the valve is not connected, be sure to connect the End Plate R (on the

Output Block side) at the right end of the manifold.

Installation example Dimensions with solenoid valves unconnected [Unit: mm]

1

2

3

4

5

6

7

8

9

10

L

114

135

156

177

198

219

240

261

282

303

L

m

[mm]

* Each dimension shows the unit without solenoid valves connected and with an End Plate

R (on the Output Block side) connected. Standard settings of L dimensions are with 10
or less m blocks. Ask SMC sales for the setting with over 10 blocks mounted.
Refer to the individual specifications for the dimensions when the solenoid valves are
connected.

Wiring (power supply, communication, input/output) and piping are all in one direction.
Space for wiring and piping is required in that direction.

SI Unit

For high

wattage load

EX9-OEP1

SI Unit

Power
Block

EX9-PE1

For high

wattage load

EX9-OEP1

SI Unit

For high

wattage load

EX9-OEP1

For high

wattage load

EX9-OEP1

For high

wattage load

EX9-OEP1

Power
Block

EX9-PE1

Power
Block

EX9-PE1

For high

wattage load

EX9-OEP1

Power
Block

EX9-PE1

SI Unit

SI Unit

SI Unit

For low

wattage load

EX9-OET1

For low

wattage load

EX9-OET1

Power
Block

EX9-PE1

For low wattage load

EX9-OET1

0

0

1

1

EX250

EX250

SOL

SOL

NS

NS

PWR

PWR

SETTINGS

SETTINGS

1

1

0

0

MS

MS

0

0

1

1

0

0

1

1

66

L = 21 x m + 93

* The number of Input Blocks + The number of Output Blocks + The number of Power Blocks : m

The number of

Input Blocks

The number of

Output Blocks

Mounting hole for 4-M4

Thickness : 13.2