Electrical Specifications
Electrical Connections
1. Initiating device circuits:
Voltage range
20-24.5 VDC
Supervisory current
4mA max. capacitor EOL
9mA max. resistor EOL
Alarm current
180mA max. per zone
2. Initiating devices per zone:
Up to 30 detectors, any combination of those in No. 3
below. Up to five waterflow switches may be used.
Any number of direct shorting devices may be used.
Wiring may be Style D (Class A) or Style B (Class B).
3. The UL identifiers for compatibility are the same as the
model names specified below. Compatible
Siemens Fire Safety detectors are:
Detector
Installation Instructions
DI-3/3H
P/N 315-081943
DI-A3/A3H
P/N 315-081943
DI-4A/4H
P/N 315-085257
DI-6
P/N 315-085257
DI-B3/B3H
P/N 315-086590
P/N 315-086591
P/N 315-086592
PE-11/PE-11T
P/N 315-094198
DT-11
P/N 315-095429
PE-3000/3000T
P/N 315-086441
PE-3/3T
P/N 315-086545
PBA-1191
P/N 315-094912
4. All circuits are power limited to NFPA 70 per NEC 760.
Each detector or group of detectors must use a two
wire circuit of at least 18 AWG thermoplastic fixture
wire enclosed in conduit, or 18 AWG limited energy
shielded cable without conduit, if permitted by local
building codes.
5. Total circuit resistance must not exceed 70 ohms, 40
ohms if relay bases are used.
Ordering Information
Dimensions
Refer to Installation Instructions P/N 315-090726