Installing the Humidifier Control to Operate Manually


If it is not possible to use the outdoor temperature sensor, or if the homeowner wants to
control the humidifier manually, Compustat can be reconfigured for manual operation.
(See Figure 9.)

1. Locate the three-pin arrangement marked “AUTO/MAN”, protruding from the con-

trol board (directly to the right of the wiring connections).

2. Pull upward to remove the black, two-pin connector from the auto position. Rein-

stall it in the manual position (on the center and right-hand pins).

NOTE:

Do not attach sensor wire to the blue wiring connection block.

3. Follow Steps 8 and 9 to complete the wiring. Apply the manual-mode faceplate to

the Compustat cover. Reattach the cover to the base and reinstall the knob.

System Checkout


1. To conduct a system test, be sure that 24 VAC is applied to the 24 VAC terminals of the humidifier control.
2. Reattach

the

Compustat cover and knob to the base.

3. Activate the furnace blower and confirm that the thermostat is calling for heat.
4. Rotate the knob on the humidifier control clockwise (

3

) to the “Test” position.

• If everything is set up correctly, the humidifier should begin operating. In “Test” mode, Compustat will operate for

approximately one minute.

• If the humidifier does not activate properly in “Test” mode, refer to the Troubleshooting Guide, below.

5. Set the humidifier control.

• If the home is occupied, set the humidifier control knob to “5”. (For manual operation, set the knob to “35%”.)
• If the home is vacant, turn the humidifier control knob counterclockwise (

4

) to “Off”.

6. Tell the homeowner to refer to the Compustat Operating Instructions for direction regarding initial adjustment.

Troubleshooting Guide

(applies to automatic and manual operation, unless otherwise indicated)


P

ROBLEM

S

OLUTION

(

S

)


Humidifier does not operate

Make sure the furnace blower is operating and the thermostat is calling for

in “Test” mode heat.

Confirm that the outdoor temperature sensor is connected to the “Outdoor

Temperature Sensor” terminals on the humidifier control. (For manual op-
eration, make sure the jumper pins are positioned correctly.)

Check the wiring diagrams (Figures 6-8) for correct installation.

Check the voltage at the humidifier control “24 VAC” terminals. (Voltage

should be between 22 and 30 VAC.)

Check the Model A50 relay (if used) for proper installation. (The relay is to

be wired to the “Out” circuit only!)

• Make sure the control knob has not been left in the “Test” position. (In

“Test” mode, the humidifier will not continue to operate after approximately
one minute.)

Humidifier operates only in

Check the resistance of the sensor by removing the leads from the humidifier

“Test” mode

control terminals, and measuring the resistance across the wires with an

ohmmeter. Compare the reading to the temperature/resistance chart, which

follows.

Temp.

Resistance

Figure 9

Automatic

Manual