Support, Supporting steel plan, Gh h w – SPX Cooling Technologies Marley Aquatower User Manual
Page 5: Option one, Option two, Diameter holes, Anchor bolt 1" 1" anchor bolt, Anchor bol t anchor bol t, Support (by others) tower collection basin 5/8, Diameter holes tower collection basin

5
1. Use this bulletin for preliminary layouts only. Obtain current drawings
from your Marley sales representative or your local distributor.
2. Purchaser to provide tower supports complete with holes and bolts for
anchorage. All supports must be framed flush and level at top. Maxi-
mum deflection to be 1/360th of span, not to exceed 1/2" (13mm).
3. Maximum weight occurs with basin full to overflow level at shutdown.
Actual operating weight varies with GPM and piping scheme.
4. Wind loads are based on 30 psf and are additive to operating loads.
Reactions due to wind loads exceed those resulting from seismic loads
based on the 1997 UBC code, Zone 4 and an Importance Factor of
1.00 per Section 1634—Towers Not on a Building.
/ Support /
F
5/8"
DIAMETER HOLES
A
G
H
H
L
W
ANCHOR
BOLT
NORMAL
GAUGE
1"
TOWER
COLLECTION BASIN
AIR INLET FACE
AIR INLET FACE
1"
1"
ANCHOR
BOLT
CL
CL
F
L
ANCHOR
BOLT
1"
1"
ANCHOR
BOLT
CL
CL
ANCHOR BOL
T
ANCHOR
BOL
T
C L
C L
G
H
H
W
ANCHOR BOL
T
ANCHOR
BOL
T
C L
C L
SUPPORT
(BY OTHERS)
TOWER
COLLECTION
BASIN
5/8"
DIAMETER HOLES
TOWER
COLLECTION BASIN
B
NORMAL
GAUGE
MIN. BEARING WIDTH
AT EACH ANCHOR BOLT
2"
SUPPORT
(BY OTHERS)
TOWER
COLLECTION
BASIN
SUPPORTING STEEL PLAN
OPTION ONE
VIEW B
SECTION A
SUPPORTING STEEL PLAN
OPTION TWO
Tower
Model
Dimensions
Shipping Weight
lb
Maximum
Operating
lb
Maximun
Operating Load
at Anchor
lb
Wind Load
lb
L
W
F
G
H
Max. Vertical
Reaction at Anchor
Max. Horizontal
Reaction at Anchor
490A-490B
2'-11
1
⁄
2
"
3'-4
1
⁄
8
"
2'-9
1
⁄
2
"
3'-0"
2
1
⁄
16
"
437
756
185
180
115
492A-492B
3'-11
1
⁄
2
"
4'-1
5
⁄
8
"
3'-9
1
⁄
2
"
3'-6"
3
13
⁄
16
"
742
1396
349
355
210
493A-493B
5'-11
1
⁄
2
"
4'-1
5
⁄
8
"
5'-9
1
⁄
2
"
3'-6"
3
13
⁄
16
"
982
1995
499
525
285
494A-49B
5'-11
1
⁄
2
"
5'-6
1
⁄
8
"
5'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
1398
2948
737
555
355
495A-495B
7'-11
1
⁄
2
"
5'-6
1
⁄
8
"
7'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
1758
3853
963
745
470
496A-496B
9'-11
1
⁄
2
"
5'-6
1
⁄
8
"
9'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
2096
4751
1188
1095
640
Models with Vertical Discharge Hood Option
494A-494C
5'-11
1
⁄
2
"
5'-6
1
⁄
8
"
5'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
1798
3348
837
700
515
495A-495B
7'-11
1
⁄
2
"
5'-6
1
⁄
8
"
7'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
2133
4233
1058
745
515
496A-496B
9'-11
1
⁄
2
"
5'-6
1
⁄
8
"
9'-9
1
⁄
2
"
5'-0"
3
1
⁄
16
"
2596
5251
1313
1095
640
Use this data for preliminary layouts only.
Obtain current drawing from your Marley sales
representative.
The Marley UPDATE web-based selection software
—available at spxcooling.com provides
Aquatower model recommendations based on
customer's specific design requirements.