Johnson Controls TCGD30 User Manual
Page 9

415571-UTG-C-0309
Johnson Controls Unitary Products
9
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TGCGD30S4(3,4)S1
INDOOR COIL MODEL NO.
FC/MC/PC35
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
28.4 31.4 30.8 33.1 34.4 29.8 31.8 31.4 33.4 34.5 31.2 32.3 32.1 33.7 34.7
S.C.
28.8 25.8 21.7 21.2 16.0 30.4 28.2 23.6 22.6 17.1 31.9 30.7 25.4 24.0 18.1
KW
1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
75
T.C.
26.4 28.8 28.2 30.9 32.6 27.9 29.7 28.9 31.4 32.8 29.5 30.5 29.6 31.8 32.9
S.C.
26.9 24.7 20.5 20.3 15.4 28.5 27.1 22.6 22.0 16.4 30.2 29.5 24.6 23.7 17.5
KW
1.8 1.8 1.8 1.9 1.9 1.8 1.8 1.8 1.9 1.9 1.9 1.9 1.9 1.9 1.9
85
T.C.
24.4 26.3 25.6 28.8 30.9 26.0 27.5 26.4 29.3 31.0 27.7 28.7 27.1 29.8 31.2
S.C.
24.9 23.6 19.4 19.4 14.7 26.6 26.0 21.6 21.4 15.8 28.4 28.4 23.9 23.4 16.8
KW
2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.0 2.1 2.0 2.0 2.0 2.1 2.1
95
T.C.
22.4 23.8 23.0 26.7 29.1 24.2 25.3 23.8 29.0 29.3 26.0 26.9 24.7 27.9 29.4
S.C.
22.9 22.5 18.2 18.5 14.1 24.8 24.9 20.7 21.2 15.1 26.7 27.3 23.1 23.1 16.2
KW
2.1 2.1 2.1 2.2 2.3 2.2 2.2 2.2 2.2 2.3 2.2 2.2 2.2 2.2 2.3
105
T.C.
20.5 21.8 20.4 23.7 26.3 22.0 23.1 21.3 24.3 26.4 23.6 24.5 22.1 24.8 26.4
S.C.
21.0 20.7 17.1 17.4 13.2 22.6 22.7 19.1 19.7 14.3 24.3 24.7 21.0 22.0 15.4
KW
2.3 2.3 2.3 2.4 2.4 2.4 2.4 2.3 2.4 2.5 2.4 2.4 2.3 2.4 2.5
115
T.C.
18.6 19.8 17.9 20.9 23.5 19.9 21.0 18.8 21.4 23.5 21.2 22.2 19.6 21.8 23.6
S.C.
19.1 18.9 15.9 16.4 12.3 20.5 20.5 17.5 18.6 13.5 22.0 22.2 19.1 20.9 14.7
KW
2.5 2.5 2.4 2.5 2.6 2.5 2.5 2.5 2.5 2.6 2.6 2.6 2.5 2.6 2.6
125
T.C.
16.8 17.9 15.4 18.1 20.7 17.8 18.9 16.2 18.5 20.7 18.9 19.9 17.1 18.8 20.7
S.C.
17.3 17.2 14.8 15.3 11.4 18.4 18.4 16.0 17.6 12.6 19.6 19.6 17.1 19.8 13.9
KW
2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.6 2.7 2.8 2.7 2.7 2.7 2.7 2.8
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
–
FC/MC/PC35
1.00 1.00 1.00
–
FC/MC/PC37
1.00 1.00 1.00
–
FC/MC/PC43
1.00 1.00 1.00
–
HC36
1.00 1.00 1.00
–
HC42
1.00 1.00 1.00
AHP30
–
1.00 1.00 1.00
AHP36
–
1.00 1.00 1.00
AHX30
–
1.01
1.06
0.95
AHX36
–
1.03
1.06
0.95
MA12B
FC/MC35B
1.00 1.00 1.00
MA12B
FC/MC43B
1.00 1.00 1.00
F4FP040
–
1.00 1.00 1.00
F6FP030
–
1.01
1.03
0.97
F6FP036
–
1.01
1.02
0.93
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*A12
FC/MC/PC32A
1.01
1.02
1.01
T*(8,L)X*B12
FC/MC/PC35B
1.03
1.09
0.99
T*(8,L)X*C16
FC/MC/PC35C
1.03
1.09
0.95
T*(8,L)X*C20
FC/MC/PC35C
0.99
0.98
0.91
T*9X*B12
FC/MC/PC35B
1.03
1.09
0.94
T*9X*C16
FC/MC/PC35C
1.03
1.07
0.94
T*(8,L)X*A12
FC/MC/PC37A
1.03
1.09
0.99
T*(8,L)X*B12
FC/MC/PC43B
1.03
1.09
0.95
T*(8,L)X*C16
FC/MC/PC43C
0.97
0.92
0.89
T*(8,L)X*C20
FC/MC/PC43C
1.02
1.01
0.94
T*9X*B12
FC/MC/PC43B
1.03
1.09
0.99
T*9X*C16
FC/MC/PC43C
1.03
1.09
0.95
T*9X*C20
FC/MC/PC43C
0.97
0.92
0.89