Additional static resistance – Johnson Controls R-410A User Manual
Page 57

333496-BTG-E-0610
Johnson Controls Unitary Products
57
Additional Static Resistance
Size
(Tons)
Model
CFM
Wet Indoor Coil
Economizer
1
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter/Frame Kit
Electric Heat
024
(2.0)
BUZ
BUX
BUQ
500
0.01
0.00
0.01
0.02
600
0.01
0.00
0.02
0.03
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
030
(2.5)
BUZ
BUQ
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.07
0.03
0.17
-
036
(3.0)
BUZ
BUX
BUQ
700
0.01
0.00
0.02
0.03
800
0.01
0.01
0.02
0.03
900
0.01
0.01
0.02
0.04
1000
0.02
0.01
0.02
0.04
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
042
(3.5)
BUZ
BUQ
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.05
0.05
0.04
0.09
1600
0.06
0.06
0.05
0.10
048
(4.0)
BUZ
BUX
BUQ
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12
060
(5.0)
BUZ
BUX
BUQ
1100
0.03
0.01
0.03
0.05
1200
0.04
0.02
0.03
0.06
1300
0.04
0.03
0.03
0.07
1400
0.04
0.04
0.03
0.08
1500
0.04
0.05
0.04
0.09
1600
0.04
0.06
0.05
0.10
1700
0.05
0.07
0.05
0.11
1800
0.05
0.07
0.06
0.11
1900
0.06
0.08
0.06
0.11
2000
0.07
0.08
0.07
0.12