R-410A SYSTEM CHARGING PROCEDURE

PROCEDURES:

1. Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of inter-

connecting line tubing.

2. Verify the TXV or orifice and additional charge required for specific evaporator coil in the system using the above table.
3. Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electri-

cal Data Table.

4. For TXV match charge weight needs to be weighed in for specififc coil match and lineset length.
5. Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for

evaporator + adder for line set.

AHP42C3X

AHP/SHP60D3X

1

AV24B3X

3

AV36C3X

25

19

15

AV/SV48D3X

9

0

1

AV/SV60D3X

0

1

0

F4FP024

0

F4FP030

3

0

F4FP036

8

5

F4FP040

12

8

F4FP042

8

0

F4FP045

9

2

F5FP048

20

10

11

F5FP060

20

10

11

F4FV060

9

10

1

FOOTNOTES:

1. Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.
2. PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.
3. A TXV kit must be used with these coils to obtain system performance. Note: If a TXV is factory installed on the coil, it must be replaced

with the listed TXV

4. Refer to Technical Guide for actual system performance and matches.

Additional R-410A Charge / Orifice Size for Various Matched Systems (Continued)

Outdoor Unit

TCGF24S41S1

TCGF30S41S1

TCGF36S41S1

TCGF42S41S1

TCGF48S41S1

TCGF60S41S1

Required Orifice or TXV

1

1TVM902

1TVM903

1TVM903

1TVM903

1TVM905

1TVM906

Factory Charge, lbs-oz

3 - 2

3 - 7

3 - 10

4 - 4

4 - 9

5 - 9

Indoor Coil

2,3,4

Additional Charge, Oz

See Caution below

See Caution below

See Caution below

See Caution below

See Caution below

See Caution below

See Caution below

See Caution below

See Caution below

If the F*FP Air Handler used has a with a factory installed R-22 TXV it MUST BE CHANGED OUT to a R-410A TXV or a orifice for proper operation.
If the TXV is not changed out system damage will occur.