beautypg.com

IDEAL INDUSTRIES 36 User Manual

Page 21

background image

Steel shell construction

Natural gas, oil fired or dual fuel

One or two stage operation

High efficiency 91% net (82% gross)

Reverse flame combination chamber design

Easy to install and service

Meets Building Regulations 2006 (Part L2)

Model 170

240

290

340

420

510

630

760

870

970

1100

1320

1570

1850

2200

2650

3000

3500

Output (kW)

170

240

290

340

420

510

630

760

870

970

1100

1320

1570

1850

2200

2650

3000

3500

Height

1272

1272

1372

1372

1542

1542

1542

1622

1622

1622

1622

1622

1732

1732

1892

1892

2080

2340

Width

820

820

860

860

890

890

890

1122

1122

1122

1352

1352

1462

1462

1622

1622

1670

1920

Depth

1214

1474

1411

1541

1606

1801

2113

1989

2184

2379

2346

2686

2781

3151

3225

3545

3835

3879

Flow/Return Connections (DN flange)

65

65

80

80

100

100

100

125

125

125

150

150

175

175

200

200

200

200

Flue Size (mm)

200

200

250

250

250

250

250

350

350

350

400

400

450

450

520

520

570

620

Maximum Working Pressure (bar)

6

Water Content (L)

190

251

264

298

398

462

565

671

753

836

1040

1242

1418

1617

2086

2324

2553

4862

Approx Dry Weight (kg)

435

510

588

629

796

919

1047

1341

1447

1553

1821

2030

2780

3280

4145

4465

5110

6700

Front (mm)

Same length as boiler

Back (mm)

500

Side - non hinge (mm)

100

Right (mm)

200 + burner length

General Data Vanguard L (130 - 3500)

Boiler
Clearances

Vanguard L

130 - 3500kW

21

This manual is related to the following products: