Tumblers – T30 and T45

4-08-43

13

IMPORTANT: For best performance provide an

individual exhaust duct for each tumbler. Do not

install a hot water heater in a room containing

tumblers. It is better to have the water heater in a

separate room with a separate air inlet.

Individual Venting

For maximum efficiency and performance, it is preferred

to exhaust tumbler(s) individually to the outdoors.

IMPORTANT: At no point may the cross sectional

area of installed venting be less than the cross

sectional area of the exhaust outlet of the tumbler.

The exhaust duct must be designed so the static back

pressure measured 12 inches (305 mm) from the

exhaust outlet does not exceed the maximum

allowable pressure specified on the installation sticker

on the rear of the tumbler.

NOTE: Static back pressure must be measured

with both pockets running.

The maximum allowable length venting of the same

diameter as the exhaust thimble is 14 feet (4.3 m) and

two 90° elbows or equivalent. If the equivalent length

of a duct required for an installation exceeds the maximum

allowable equivalent length, the diameter of a round duct

must be increased by 10% for each additional 20 feet

(6.1 m). Cross section area of a rectangular duct must

be increased by 20% for each additional 20 feet (6.1 m).

Refer to Table 1 to determine equivalent venting.

NOTE: The maximum length of a flexible metal

duct must not exceed 2.4 m (7.87 ft.) as required to

meet UL2158, clause 7.3.2A.

Example: A 12 inch (305 mm) diameter duct’s

equivalent length of 14 feet (4.3 m) of duct and two

90° elbows is:
Equivalent Length = 14 feet + (2) 90° elbows

= 14 feet + 14 feet + 14 feet

= 42 feet (12.8 m)

With the tumbler in operation, and both pockets

running, airflow at any point in the duct should be at

least 1200 feet per minute (366 meters per meter) to

ensure that lint remains airborne. If 1200 feet per

minute cannot be maintained, schedule monthly

inspections and cleaning of the ductwork.

Duct

Diameter

Equivalent Length of Rigid

Straight Duct

10 in. (254 mm)
12 in. (305 mm)
14 in. (355.6 mm)
16 in. (406.4 mm)
18 in. (457.2 mm)

One 90° elbow = 11.6 ft. (3.5 m)
One 90° elbow = 14 ft. (4.3 m)
One 90° elbow = 16 ft. (4.9 m)
One 90° elbow = 18.7 ft. (5.7 m)
One 90° elbow = 21 ft. (6.4 m)

Equivalent Length (feet) = 1.17 x Duct Diameter (inches)

Table 1