Clearances, Height requirements – Monessen Hearth BUF400 User Manual

Page 9

background image

61D1013

9

12"

10"

8"

6"

2

1

/

2

"

12"

16"

19"

21"

23"

CLEARANCES

and

HEIGHT REqUIREMENTS

4. Mantel clearances: The canopy supplied with the unit

must be installed. If a combustible mantel is installed,
it must meet the clearance requirements as shown in
Figure 5.

5. Floor clearance: This inner chamber firebox floor must be installed at least 5" above any combustible

flooring material, such as carpeting or asphalt tile, which is closer than 14" to the base of the firebox. See
Figure 6.

Or
The inner chamber firebox floor may be installed nearer to the floor if a minimum of 14" of noncombustible

material such as slate or marble is installed between the base of the firebox and the combustible flooring.
See Figure 7.

Figure 5 - Mantel Clearances

Figure 6 - Minimum Clearance above

Combustible Flooring

Figure 7 - Minimum Clearance above Combustible

Flooring with Non-Combustible Material Installed at

Base of Fireplace

Non-Combustible

Material

5" Minimum

14" Minimum

Can Be

Less than 5"

Non-Combustible

Material