English, System specifications, Output non-battery operation input – Minuteman UPS E700RM1U User Manual
Page 21: Output battery operation

20
English
Default 120VAC User selectable 120/127VAC
700VA
490W
1500VA
900W
1000VA
700W
Protection
Waveform Type
Over-Current, Short-Circuit Protected and Latching Shutdown
Sine Wave
Frequency
50/60Hz, +/-0.1Hz (unless synchronized to utility)
Nominal Voltage
Maximum Power Capacity
2-6 mS Typical
>93% (Full Load)
Resettable Circuit Breaker
50 or 60 Hz, +/-6Hz, autosensing
0 - 165VAC
85 - 150VAC
120VAC: 105 - 132VAC (127VAC: 105 - 137VAC)
Transfer Time
Efficiency (Line Mode)
Input Protection
Frequency Limits
Voltage Range
Acceptable Input voltage
E1500RM1U
E1000RM1U
E700RM1U
Model Number
SYSTEM SPECIFICATIONS
Voltage Range
Topology
Line-Interactive, Sine Wave
OUTPUT NON-BATTERY OPERATION
INPUT
Number of Phase
Single (1
∅
2W +G)
Nominal Voltage
120VAC
Low Voltage Transfer Point
85V resets to Utility Power at 90V or higher
High Voltage Transfer Point
150V resets to Utility Power at 145V or lower
Voltage Regulation
120VAC: -12.5% - +10% (127VAC: -17.3% - +7.8%)
Frequency Range
60Hz: 54 - 66Hz or 50Hz: 44 - 56Hz
OUTPUT BATTERY OPERATION
Voltage Regulation
Nominal +/-2% (until Low Battery Warning)
Voltage T.H.D.
<5% (Linear Load)
+/-5% @ 100% Load change in 100mS
Dynamic Response
Slew Rate
<1Hz/Second
Overload Capacity
110% for 20-Seconds
125% for 10-Seconds
150% Shutdown Immediately
<8% (Linear Load)