page 3 — 7

Owner’s Manual

3.11

Troubleshooting Guide

After having thoroughly reexamined the installation and setup of the system, and still found it un-operational, user

can follow Table 3-2 to identify a problem, its cause, and recommendations for fixing it.

Table 3-2: Troubleshooting table.

Problem

Possible Cause

Possible Solution

Display panel not illuminated

No power to system

Check AC & DC power sources.

No output voltage

SW1 not ON

Turn SW1 ON

System starts, then shuts

Overload, or shorted

Remove some of the load and

down almost immediately

output.

restart the inverter.

Power module LED turn red

Module faulted

Reset by recycling circuit breaker

Module temp. indicator on

Module fan failure

Replace module or cooling fan

Maintenance Adjustment and Troubleshooting