7. overload protection (onan-powered units) – Miller Electric 280 NT User Manual
Page 33

OM-4402 Page 29
Y Stop engine.
.
When a circuit breaker or fuse
opens, it usually indicates a
more serious problem exists.
Contact a Factory Authorized
Service Agent.
1
Circuit Breaker CB5
CB5 protects the 24 volt ac output
to Remote 14 receptacle RC1. If
CB5 opens, 24 volt ac output to
RC1 stops.
2
Circuit Breaker CB6
CB6 protects the 115 volt ac output
to Remote 14 receptacle RC1. If
CB6 opens, 115 volt ac output to
RC1 stops.
Press button to reset breaker.
3
Fuse F6 (See Parts List)
F6 protects the engine wiring sys-
tem from overload. If F6 opens,
engine will not crank.
4
Fuse F1 (See Parts List)
5
Fuse F2 (See Parts List)
Remove side panel.
F1 protects the exciter excitation
winding from overload. If F1 opens,
weld and auxiliary power output
stops.
F2 protects the stator winding from
overload. If F2 opens, weld output
stops. Auxiliary power will still be
available.
Replace any open fuses. Reinstall
cover before operating unit.
3/8 in
801 945-C / Ref. 203 073
4
Tools Needed:
2
2
3
7-7. Overload Protection (Onan-Powered Units)
1
5