OPERATION

Fan

The fan will run constantly except when a defrost is initiated, or when the evaporator temp is above

35

o

F. When in defrost mode the fan is off until the end of the defrost and the 2 minute drip time has

passed. There is 2 minutes delay after a defrost before the fan comes on. The difference of the evaporator
and room temperature of more than 9

o

F will override the fan delay.

FAN LED indicator is flashing during 2

minutes drip period.

Defrost The control uses time defrosts with four defrost per day for oil return safety. The defrost timer
begins counting on power up. For example, if a defrost is desired at 12 am, 6 am, 12m, and 6 pm then
power up the unit at any of those four times.


MANUAL DEFROST

1. Push this DEFROST

UP/DEFROST”

key for more than 5 seconds and a manual defrost will

start, if the conditions are correct, the led DEF will light up and the instrument will carry out a
defrosting cycle.

2. While in defrost, push and hold the DEFROST

key for more than 5 seconds and the

controller will end the defrost cycle. The controller will then enter drip mode for 2 minutes. The DEF
led is flashing in drip mode.

HOW TO CHANGE SET POINTS

1. Press the P

until sp-1 is displayed.


2. Push

UP

or DOWN▼ arrows to change the value.

3. To Exit: Press

SET + UP

▲ or wait 20 seconds without pressing a key.


NOTE 1: The set value is stored even when the procedure is exited by waiting the time-out to expire.

NOTE 2: Master-Bilt’s SETPOINT is set at a recommended 20

°F at the factory.

NOTE 3: If power is turned off to the unit, the set point returns to factory set value.