beautypg.com

Installation, Hot swap – MGE UPS Systems 3000 VA User Manual

Page 17

background image

51033211EN/AC

- Page 17

2. Installation

Before carrying out any connections, check that the battery circuit breaker is OFF
and that the electrical power cord to the AC-power source is disconnected.

Connection of equipment to outlets
Plug your equipment into the outlets .

Connection of equipment to a terminal block:
This type of connection must be carried out by qualified
electrical personnel.

1. Remove the terminal-block cover .
2. Insert the cable supplying the equipment through the cable
clamp .
3. Connect the three wires to the output terminal block .

Always connect the earthing wire first.

4. Remove the terminal-block cover.
5. Tighten the nut on the cable clamp .

The overall cable diameter and the cross-sectional area
of the three wires depends on the UPS rating.

Connection to the AC-power source:
1. Connect the electrical power cord to the socket
for connection to AC-power source.
2. Connect the other end of the electrical power cord
to an AC-power outlet.

2

29

1

5

33

33

Hot swap

8

32

8

2

32

33

1

Earthing wire

29

5

Phase
Neutral

Cable diameter

Cross-sectional area of each wire

Pulsar EXtreme
2000

Pulsar EXtreme
3000

From 9 to 12 mm

From 9 to 12 mm

1 to 4 mm

2

1,5 to 4 mm

2

Recommended upstream
circuit breaker

Nominal rating

(47 to 63Hz, 230V)

Maximum rating

(47 to 63Hz, 187V)

C60N 10A 2P
(maximum line
current = 9A)

C60N 16A 2P
(maximum line
current = 11A)

C60N 16A 2P
(maximum line
current = 13A)

C60N 20A 2P
(maximum line
current = 16A)

Output terminal block

This manual is related to the following products: