3. Example of safety system configuration

Example 1























Fig.3 Safety system example 1 – STOP asynchronous with EM and fault detection through A-C output.


For safety stop, configure the wiring as shown in Fig.3 above.
Note: the above wiring is configured to prevent restart in case of a fault.

The parameter No.192 must be set to ‘199’. This setting makes the A-C output to open in case of failure.

After the power-up, to reset the safety stop mode, press the START switch, and also press the STF switch,
then start the motor rotation.

In the above configuration, after reset of EM switch, drive will be in safe-state until START switch is
pressed.

ATTENTION

To prevent restart in case of recovering from input power loss of drive, 3-wired connection for STF/STOP
control is recommended.
In case of 2-wire connection and using latching type switch to short between STF and SD/PC for starting,
ensure the compliance with safety requirement for the restarting when the drive recover from input power
loss.