Definition of PLC Read/Write Address

a. Registers

V1.02 Revision November, 2011

111

Format

Type

Word No. (n)

Read/Write Range

Data

Length

Note

Xn

X0 – X7FF

Input

Word

3

Yn

Y0 – X7FF

Output

Word

3

Bn

B0 – BFFF

Link Relay

Word

3

Mn

M0 – M8176

Internal Relay

Word

3

SMn

SM9000 – SM9240

Special Internal Relay

Word

4

Ln

L0 – L2032

Latch Relay

Word

3

Fn

F0 – F2032

Annunciator

Word

3

TNn

TN0 – TN999

Timer Value

Word

CNn

CN0 – CN999

Counter Value

Word

Dn

D0 – D8191

Data Register

Word

SDn

SD9000 – SD9255

Special Data Register

Word

Rn

R0 – R8191

File Register

Word

Wn

W0 - WFFF

Link Register

Word

b. Contacts

Format

Type

Bit No. (b)

Read/Write Range

Note

Input

Xb

X0 – X7FF

Output

Yb

Y0 – Y7FF

Link Relay

Bb

B0 – BFFF

Internal Relay

Mb

M0 – M8191

Special Internal Relay

SMb

SM9000 – SM9255

Latch Relay

Lb

L0 – L2047

Annunciator

Fb

F0 – F2047

Timer Contact

TSb

TS0 – TS999

Timer Coil

TCb

TC0 – TC999

Counter Contact

CSb

CS0 – CS999

Counter Coil

CCb

CC0 – CC999

NOTE

1)

a. The mode switch setting of AJ71UC24-R2 communication is 4 (Form 4), station

number can only be 0.