6.1 Technical specifications

(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.

When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is IEC/EN
60898-1 standard compliant;

When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.

This product is designed for IT power distribution system.

Evolution S

1250

Evolution S

1750

Evolution

2000

Evolution S

2500

Evolution S

3000

Output power

1250VA/1150W

1750VA/1600W

2000VA/1600W

2500VA/2250W

3000VA/2700W

AC input power

Rated input voltage

Input-voltage range

Input-frequency range

Single phase 220~240 V

160 V to 294 V

(1)

47 to 70 Hz (50 Hz system), 56.5 to 70 Hz (60 Hz system)

(2)

Output on battery power

Voltage

Frequency

230 V (+6/-10%)

(3)

50/60 Hz ±0.1%

Battery (sealed lead acid,
maintenance free)

Standard

Additional modules possible

(up to 4 EXB)

4 x 12 V

7.2 Ah

4 x 12 V - 9 Ah

6 x 12 V

7.2 Ah

6 x 12 V

9 Ah

Evolution S EXB 1250/1750

(4)

No

Evolution EXB S 2500/3000

(5)

Environment

Operating temperature

range

Storage temperature range

Relative humidity

Noise level

0 to 40°C

-25°C to 40°C

20 to 90% (without condensation)

< 45 dBA

< 50 dBA

Filter

Transformer

(AVR)

Charger

Inverter

Battery