VENTING

RECOMMENDED VENTING CLEARANCES PER THE NATIONAL FUEL GAS CODE*

All venting must be properly supported. The Munchkin is not intended to support any venting
whatsoever.
All piping, glue, solvents, cleaners, fittings and components, must conform to ASTM
(American Society for Testing and Materials), and ANSI (American National Standards Institute). It is
recommended that you use one of the optional vent kits specifically designed for Munchkin installa-
tions, available from Heat Transfer Products, Inc.
Example: Installation requires the following material for both inlet and exhaust piping for the
Munchkin 199VWH and the 399VWH.

Required: 4 Pcs. 90 degree elbow (4 x 5 = 20 Equivalent Feet) = 20 Equivalent Feet

Required:

20' of Plastic PVC Pipe (20 x 1 = 20 Equivalent Feet) = 20 Equivalent Feet

Total Friction Loss in Equivalent Feet (20 + 20 = 40 Equivalent Feet) = 40 Equivalent Feet

C. LONGER VENT RUNS

CAUTION

Flue Gas will condense as it exits the vent termination. This condensate can freeze on
exterior building surfaces which may cause discoloration of these surfaces.
Consideration should be given to the plume of condensation that exits the exhaust
which may affect the cosmetic appearance of the building.

12 in.minimum

Forced air
inlet

Grad

e

3 ft.minimum

Less

than 10 ft.

terminal
(see 10.8.1)*

draft vent

Mechanical

C

12 in.minimum

Direct vent terminal clearance
Minimum clearance, C

Input (Btu/hr)

4 ft.minimum

12 in.minimum

minimum

vent terminal

Mechanical draft

(see 10.8.2)*

4 ft.

Clearance (in.)

10,000 or less
10,001 to 50,000

Over 50,000

(see 10.8.3)*

6
9

12

For SI units: 1 ft = 0.305 m; 1 in. = 25.4 mm;
1 Btu/hr = 0.293 W

EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT VENTING SYSTEM

* REFERENCE: THE NATIONAL FUEL GAS CODE 2002 EDITION

*IMPORTANT NOTE

HEAT TRANSFER

PRODUCTS

RECOMMENDS A

MINIMUM

CLEARANCE OF 4

FEET WHERE THE

PLUME CAUSED BY

THE UNIT MAY

OBSTRUCT VIEWS

OR AFFECT THE

COSMETIC LOOK OF

THE BUILDING.

NOTICE

Do not exceed the 125 foot maximum requirement for (intake plus exhaust piping
added together). Consider fitting allowance shown in friction loss equivalent table on
the following page.