beautypg.com

Macurco CM-S1 User Manual

Page 4

background image

Document #679-800-001

Page 4 of 4

Rev. 1.1, Jan 9, 2006

CM-S1

N.O.

VIO

N.C.

BLU

COM YEL

BLK

RED

12/24V

GND

SPDT
Alarm

relay

CM-S1

N.O.

VIO

N.C.

BLU

COM YEL

BLK

RED

12/24V

GND

SPDT
Alarm

relay

UL

LISTED

12VDC

ALARM

UL LISTED

12VDC

POWER SUPPLY

POWER

N.O. initiating

circuit

12/24V GND

Battery-backed 12 or 24
VDC Power Supply. Fuse
or current limit at 0.5 A for
each CM-S1

UL Listed Alarm Control Panel

CM-S1

N.O.

VIO

N.C.

BLU

COM YEL

BLK

RED

12/24V

GND

SPDT
Alarm

relay

CM-S1

N.O.

VIO

N.C.

BLU

COM YEL

BLK

RED

12/24V

GND

SPDT
Alarm

relay

E.O

.L.R.

WIRING DIAGRAMS

ENSURE POWER IS OFF WHEN CONNECTING THE PIGTAIL CABLE TO THE CM-S1

TYPICAL CONNECTION OF TWO CM-S1's TO AN ALARM CONTROL PANEL

1.

The CM-S1 is for use with UL Listed Alarm Control Panels (Fire or Fire/Burglar type or Critical Process Management Equipment)
that have 12 to 24 VDC alarm initiating circuits.

2.

The Alarm Control Panel (Fire or Fire/Burglar type or Critical Process Management Equipment) must be dedicated to CO detection or
have alarm devices that provide a distinctive alarm for carbon monoxide detection. Do not connect the CM-S1 to Fire Alarm Circuits.

3.

The CM-S1 is intended for installation in buildings in non-hazardous locations such as residences, retail stores, office buildings and
institutional buildings.

4.

The CM-S1 is NOT intended for use in industrial applications such as refineries, chemical plants, etc. The CM-S1 is NOT intended
for use in parking garages, as the controller for exhaust systems.

5.

LOCATION: Place the unit at a level where people breathe: about 5 feet (1.5 meters) above the floor. Mount the CM-S1 in a vertical
position on a wall or column. Do NOT mount the CM-S1 in a corner.

6.

SPACING: Use the same spacing as for smoke detectors – 30 foot (9 meters) centers, 900 sq. feet (83 sq. meters) per detector.

7.

INSTALLATION: See page 1.

8.

The alarm control panel zone inputs must be terminated with end of line resistors (E.O.L.R.), which are provided with the panel.

9.

When using the CM-S1 with normally closed initiating circuits, use the "N.C." and "COM" alarm relay connections.

The CM-S1 has not been evaluated as a stand-alone unit by U.L.

Alarm Relay: SPDT,
1.0 Amps., 60VDC, 60 VA
dry contacts, no polarity

UL Listed Class 2

Power Source:

12-24 VDC, 1 VA

!

CM-S1 CONTROLLING A REMOTE ALARM