21

English

Battery Type

24VDC

Typical Recharge Time

50 or 60 Hz, +/-6Hz, autosensing

115VAC: 90 - 130VAC (230VAC: 180 - 260VAC)

2.6 Amps

27.6VDC +/-5%

Frequency Limits

DC Voltage

Voltage Range

EDBP24XL

Model Number

SYSTEM SPECIFICATIONS

AC Current

Format

Rack/Tower Convertible

CHARGER OUTPUT

CHARGER INPUT

Number of Phases

Single (1

2W +G)

Nominal Voltage

115/230VAC (dipswitch selectable)

Input Protection

Resettable Circuit Breaker

DC Current

2.4 Amps

BATTERY SYSTEM

Typical Battery Life

System Current

40 Amps

4 - 12V8.5Ah

Battery Qty/Rating

EDBP72XL

82.8VDC +/-5%

System Voltage

Sealed, Non-Spillable, Maintenance Free, Value Regulated, Lead Acid

3-5 years, depending on discharge cycles and ambient temperature

8-hours from total discharge

72VDC

6 - 12V8.5Ah

Output Protection

Resettable Circuit Breaker

PHYSICAL

Weight - Net

Size - Net
L X W X H

Size - Shipping
L X W X H

Weight - Shipping

55.0 lbs
25.0 Kgs

17.0 x 17.3 x 3.5"
432 x 440 x 89 mm

23.6 x 20.0 x 9.0"
600 x 508 x 230 mm

64.0 lbs
29.0 Kgs

REGULATORY COMPLIANCE

Safety and Approvals

EMC Verification

UL1778, cUL (CSA 22.2 no. 107.1)

FCC Class A, CE certified

49.0 lbs
22.0 Kgs

39.6 lbs
18.0 Kgs

EDBP48XL

55.2VDC +/-5%

48VDC

8 - 12V8.5Ah

66.0 lbs
30.0 Kgs

75.0 lbs
34.0 Kgs

13.1 x 17.3 x 3.5"
335 x 440 x 89 mm

23.6 x 20.0 x 9.0"
600 x 508 x 230 mm