OM-2236 Page 14

4-7.

Selecting And Preparing Weld Output Cables

10 ft (3 m)

1

Total Cable

Length In Weld

Circuit = 20 ft (6 m)

10 ft (3 m)

For Example,

2

4

3

2

Tools Needed:

sb6.1 11/92 − S-0653

1

Weld Output Cable

Determine total cable length in weld
circuit and maximum welding am-
peres. See Section 4-8 to select
proper cable size.

Use shortest cables possible.

Do not use damaged cables.

2

Terminal Lug

Use lugs of proper amperage
capacity and hole size for connect-
ing to work clamp, electrode holder,
and weld output terminals.

3

Insulated Electrode Holder

Install according to manufacturer’s
instructions.

4

Work Clamp

Install onto work cable.

4-8.

Weld Cable Sizes

Total Cable (Copper) Length In Weld Circuit Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Welding

Amperes

10 To 60%

Duty Cycle

60 Thru 100%

Duty Cycle

10 Thru 100% Duty Cycle

100

4

4

4

3

2

1

1/0

1/0

150

3

3

2

1

1/0

2/0

3/0

3/0

200

3

2

1

1/0

2/0

3/0

4/0

4/0

250

2

1

1/0

2/0

3/0

4/0

2-2/0

2-2/0

300

1

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

350

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

2-4/0

400

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

2-4/0

500

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-3/0

600

3/0

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-4/0

3-4/0

*Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere. Contact your distributor for
the mm

2

equivalent weld cable sizes.

S-0007-E