Getting started, Location, Preliminary checks – MGE UPS Systems EXB10Rack User Manual
Page 14: Connections
10
Pulsar EX
Rack: 86-153522-00
MGE UPS SYSTEMS
getting started
location
c
observe the safety rules indicated at the
beginning of this document.
preliminary checks
c
check that button 3 "
" on the front is
not pushed in;
c
check that rating shown on identification
plate 9 corresponds to the input voltage
specification and power requirement of your
application.
connections
c
use your application cord to supply
input power to Pulsar as shown.
Connect the computer cord 5 between
UPS utility power receptacle
4 , and a
nearby utility power outlet.
Note 1:
Following connection, the battery
automatically charges, whatever the position
of the ON/OFF button 3 "
" .
Note 2:
The batteries will provide full back-up time
after approximatively 8 hours of recharge
time.
Note 3:
The rating of input power cord must not be
less than the nominal input rating of
Pulsar EX10
Rack
: Use the supplied cord.
c
connection of Pulsar EXB10
Rack
battery extension module (optional):
v
check that button 3 "
" on the front of
the Pulsar EX10
Rack
is not pushed in,
v
disconnect the utility power connection
cord 5 ,
v
flip the circuit-breaker 20 of the unit to
the right (position "O"),
v
connect the battery connection cord 23
to connector 21 of the module and
connect 13 of the Pulsar EX10
Rack
,
v
if the installation has 2 battery modules,
connect the second cord 23 to connectors
21 of the second module and 22 of the
first module,
v
the use of connectors 13 , 21 and 22
is strictly limited to connecting the battery
modules to the Pulsar EX10
Rack
. Any other
connection to these connectors is prohibited
at the risk of damaging the battery and
losing the warranty,
v
flip the battery circuit-breaker 20 to the
left (position "I"),
v
if your installation is operated with MGE
UPS SYSTEMS software, update your
battery configuration with EX Tuner.
c
use IEC cords to connect your
applications to output sockets 7 .
7
Vac IN
computer
loads
utility
power
outlet
Vac IN
5
4