4.2 Hot-swapping the power module
◗
Stop the UPS with the OFF button 18 (press more than 3 seconds).
◗
Check if UPS is on bypass AC source:
led 15 is on (If led 15 is not on, do not turn the manual bypass and
call the after sales support department).
◗
Turn the manual bypass switch 7 to the BYPASS position.
◗
Switch the battery circuit breaker (s) 12 to the "0" position.
◗
Switch the Normal AC source circuit-breaker 9 to the "0" position and
wait 30 seconds.
◗
Remove the three fixing screws to free the junction Input/Output box.
◗
Disconnect the battery cables 28 and 29 from the power module.
The power module can be replaced.
The connected equipment is powered by the Bypass AC source.
18
15
7
Disconnecting the power module
9
29
28
4. Maintenance
This operation can be performed without interrupting the load.