10. electrical service guide for xmt 304 4-racks – Miller Electric Inverter Rack User Manual
Page 21

OM-818 Page 17
3-10. Electrical Service Guide For XMT 304 4-Racks
Input Voltage
230
460
575
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
200
110
90
Min Input Conductor Size In AWG/Kcmil
2
6
8
Max Recommended Input Conductor Length
In Feet (Meters)
210 (64)
301 (92)
300 (91)
Min Grounding Conductor Size In AWG/Kcmil
6
6
8
Reference: 1996 National Electrical Code (NEC).
S-0092J
3-11. Electrical Service Guide For XMT 304/EX 300 6-Racks
Input Voltage
230
460
575
Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes
300
175
125
Min Input Conductor Size In AWG/Kcmil
1/0
2
4
Max Recommended Input Conductor Length
In Feet (Meters)
215 (66)
451 (137)
467 (142)
Min Grounding Conductor Size In AWG/Kcmil
4
6
6
Reference: 1996 National Electrical Code (NEC).
S-0092J
3-12. Electrical Service Guide For XMT 456/Invision 456 Racks (Customer-Installed Only)
Input Voltage*
460
575
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
200
175
Min Input Conductor Size In AWG/Kcmil
2
2
Max Recommended Input Conductor Length
In Feet (Meters)
210 (64)
451 (137)
Min Grounding Conductor Size In AWG/Kcmil
6
8
* Due to current demands, a rack containing XMT/Invisions 456 requiring 230/460 volt input power must be connected to 460 volt input power
only.
Reference: 1996 National Electrical Code (NEC).
S-0092J