Model G0562Z/ZP, G1030Z2/Z2P (Mfg. 11/11+)
-27-
Be sure that you extend the bare copper wire
down all branches of the system. Do not forget
to connect the wires to each other with wire nuts
when two branches meet at a “y” or “t” connec-
tion.
Ensure that the entire system is grounded. if using
plastic blast gates to direct air flow, the ground-
ing wire must be jumped (
figure 44) around the
blast gate without interruption to the grounding
system.
figure 44. ground jumper wire when using
plastic blast gates and metal duct.
plastic Blast
gate
Metal Duct
Copper
ground Wire
figure 45. Flex-hose grounded to machine.
ground screw
Flex-hose
internal ground
Wire
External ground Wire
We also recommend wrapping the outside of all
plastic ducts with bare copper wire to ground the
outside of the system against static electrical build
up. Wire connections at y’s and t’s should be
made with wire nuts.
attach the bare ground wire to each stationary
woodworking machine and attach to the dust
collector frame with a ground screw as shown in
figure 45. Ensure that each machine is continu-
ously grounded to the grounding terminal in your
electric service panel.