beautypg.com

6 main circuit breaker, 7 engine protective devices, 8 specifications – Generac Power Systems 004626-5 User Manual

Page 7

background image

1.6 MAIN

CIRCUIT

BREAKER

The generator’s main circuit breaker is included with the
unit as shipped from the factory. The breaker for each
unit is described as follows:

1.7 ENGINE

PROTECTIVE

DEVICES

The engine has several safety switches that cause
it to automatically shut down under the following condi-
tions: low oil pressure, high coolant temperature, low
coolant level, engine overspeed and overcrank.

1.7.1

LOW OIL PRESSURE SWITCH

This switch is normally closed (N.C.) but is held open by
engine oil pressure during engine running. Should oper-
ating oil pressure drop below approximately 10 psi (68
kPa), the switch contacts close, and the engine shuts down
automatically (Figure 1.2).

Figure 1.2 – Engine Protective Devices

1.7.2

HIGH COOLANT TEMPERATURE SWITCH

This normally open (N.O.) thermostatic switch has a
sensing tip that is immersed in captive coolant. Should
the coolant temperature exceed approximately 121° C
(250° F), the switch contacts close, which causes the
engine to shut down automatically (Figure 1.2).

1.7.3

LOW COOLANT LEVEL SWITCH

Should the engine coolant level drop below the level of the
high coolant temperature switch, it is possible for the
engine to overheat without automatic shut down. To pre-
vent such overheating without automatic shut down, the
engine has a low coolant level sensor. If the engine coolant
drops too low, the engine automatically shuts down
(Figure 1.2).

1.7.4

OVERSPEED SHUTDOWN

The control module assembly (CMA) circuit board on
liquid-cooled units receives AC frequency (rpm) signals
directly from the stator AC power windings. Should AC
frequency exceed approximately 72 Hertz, circuit board
action will automatically shut down the engine.

1.7.5

OVERCRANK SHUTDOWN

After 90 seconds of crank-rest cycles (about seven sec-
onds cranking/seven seconds at rest), this function ends
cranking if the engine fails to start in that 90-second
span.

1.7.6

DC FUSE

This fuse is located on the front panel of the control sys-
tem. It protects the panel wiring and components from
damaging overload. Always remove this fuse before
commencing work on the generator. The unit will not
start or crank if the fuse is blown. Replace the fuse with
one of the same size, type, and rating. Generac uses an
AGC fuse rated at 15 amps.

1.8 SPECIFICATIONS

1.8.1 GENERATOR

Models ..............................................0043736, 0046265
Rated Maximum Continuous

AC Power Output (kW)*..................................................40

Rated Voltage (volts) ................................................120/240
Rated Maximum Continuous

Current at 240 Volts, Single-phase (amps)................................167

Number of Rotor Poles ........................................................4
Driven Speed of Rotor (rpm) ........................................1,800
Type of Stator ........................................................Four-wire
Rotor Excitation System ..................................Direct Excited

Brush-type System

Stator Insulation ....................................................Class “H”
Rotor Insulation ......................................................Class “F”

*Rated power of generator is subject to and limited by such factors as ambient tempera-

ture, altitude, engine condition and other factors. Engine power will decrease about 3.5

percent for each 1,000 feet above sea level; and also will decrease an additional 1 percent

for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of the gener-

ator is limited by maximum engine power.

‹

‹

‹

‹

‹

‹

Section 1 — General Information

Guardian Liquid-cooled 40 kW Generator

Generac

®

Power Systems, Inc.

5

Model Number

Circuit Breaker Rating

0043736

200-amp breaker

0046265

200-amp breaker

This manual is related to the following products: