Operating data – Generac Power Systems Whisper - Test UL 2200 User Manual
Page 3

COMMERCIAL 70 kW
KW RATING
70
ENGINE SIZE
6.8 Liter V-10
GENERATOR OUTPUT VOLTAGE/KW - 60 Hz
KW
AMP
CB Size
120/240V, single phase, 1.0 pf
70 LP / 68 NG
291.6 LP / 283.3 NG
300
120/208V, 3-phase, 0.8 pf
70 LP / 68 NG
243.1 LP / 236.2 NG
300
120/240V, 3-phase, 0.8 pf
70 LP / 68 NG
210.7 LP / 204.7 NG
250
277/480V, 3-phase, 0.8 pf
70 LP / 68 NG
105.3 LP / 102.4 NG
125
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase
145
480V
3-phase
160
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas
Propane
(ft3/hr.) (gal/hr.)
cu
ft/hr
Exercise
cycle
110
1.20
44.2
25% of rated load
260
2.85
104.9
50% of rated load
499
5.46
200.9
75% of rated load
696
7.62
280.4
100% of rated load
1020
11.17
411
ENGINE COOLING
Air
flow
(inlet air including alternator and combustion air)
ft3/min. 5200
System coolant capacity
US gal.
4.5
Heat rejection to coolant
BTU/hr.
287,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
205
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode
61
db(A) @ 23 feet at normal operating load
65
EXHAUST
Exhaust flow at rated output 60 Hz
cfm 557
Exhaust temp. at muffler outlet
°F
890
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
1800
HP at rated KW
60 Hz
110.7
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature
Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude
Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
OPERATING DATA
COMMERCIAL 70 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.
COMMERCIAL SERIES