Configuration – GE ACUXL16 User Manual
Page 3
Cable # Description
Belden Cable Number ( or equal)
Max. Distance
1
Communication (RS-485)
Power (24 VDC)
#9842 or Alpha #6222C, 24 AWG, 2-pair, braid overall shield AND #9409 or
Alpha #1897C, 18 AWG, 2-conductor/unshielded
4,000’ (1,220 m) 4,000’
(1,220 m)
2
Exit Request Button / Sensor
Input
#9407-22 AWG, 2-conductor (unshielded)
1,000’ (305 m)
3
Door Lock Control from
Controller or RRE
#9409-18 AWG, 2-conductor (unshielded)
1,000’ (305 m)
4
Standard Reader
Varies with type of reader/keypad. See manufacturers instructions.
varies
5
Controller to Host
Communication or other
ACU panels OR Controller to
10/100 Hub Communication
#9842 or Alpha #6222C, 24 AWG, 2-pair/braid overall shield #1583A-24 AWG,
4-pair (unshielded)
4,000’ (1,220 m) 328’
(100 m)
Configuration