2 control console components, Danger, 1 auto/off/manual switch – Guardian Technologies 004988-4 User Manual
Page 15: 2 fault indicator led, 3 15 amp fuse, 4 4.0 amp inline fuse, 5 set exercise time switch, 6 system ready led, Figure 3.1 - home standby generator panel
13
MANUAL — The control board will start and run
the generator whenever the switch is in the manual
position.
AUTO — The control board will monitor the two-
wire start circuit. When a two-wire start is issued the
control board will immediately start and run the gen-
erator. Whe the two-wire start is removed the control
board will immediately stop the generator.
NOTE:
If the generator is installed in conjunction with an
engineered GTS type transfer switch, refer to the
applicable transfer switch manual for exact oper-
ating parameters and timing sequences.
3.2
CONTROL CONSOLE
COMPONENTS
The components of a home standby generator control
console (Figure 3.1) are as follows:
3.2.1 AUTO/OFF/MANUAL
SWITCH
Use this three-position switch as follows:
• Set the switch to AUTO for fully automatic opera-
tion. See “Automatic Operation” (Section 3.6).
• Set switch to MANUAL position to crank and start
the generator engine.
• Set switch to OFF position to shut down an operat-
ing engine. With OFF selected, operation will not
be possible.
Figure 3.1 - Home Standby Generator Panel
E
US
U
F
F
E
US
U
F
(SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS)
5 FLASHING RED LED'S = EXERCISER NOT SET
FLASHING GREEN LED = NO UTILITY SENSE
TO SET EXERCISER TIME
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION.
(IN AUTO MODE ONLY) SOLID GREEN LED = SYSTEM READY, UTILITY POWER ON
OFF
EXERCISE
TIME
ON
SET
LED INDICATORS:
RED LED'S = INDIVIDUAL FAULT
MANUAL
OFF
AUTO
0E7194
OVER CRANK
AUTO/OFF/MANUAL
SWITCH
15A FUSE
MAIN
POWER
4A FUSE
BATTERY
CHARGER
SET
EXECISER
TIME
SWITCH
RED LED
GREEN LED
DANGER
With switch set to AUTO, engine can crank and
start suddenly without warning. Such automatic
start up normally occurs when utility source
voltage drops below a pre-set level. To prevent
possible injury that might be caused by such
sudden starts, set AUTO/OFF/MANUAL switch
to OFF before working on or around the unit.
Then, place a “DO NOT OPERATE” tag on control
console.
3.2.2 FAULT INDICATOR LED
This LED goes ON when one or more of the following
engine faults occurs and when engine shuts down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/RPM Sensor Loss
• High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine pro-
tection functions.
3.2.3 15 AMP FUSE
Fuse protects the control console’s DC control circuit
against electrical overload. If the fuse has melted
open because of an overload, engine cranking and
startup cannot occur. If the fuse needs to be replaced,
use only an identical 15-amp replacement fuse. (Type
AGC)
3.2.4 4.0 AMP INLINE FUSE
This fuse protects the battery charger against electri-
cal overload. If the fuse needs to be replaced, use only
an identical 4 amp replacement fuse (type AG).
NOTE:
This fuse will not remove the + battery input
power from the PCB when it opens. This means
the exercise timer will not be reset.
3.2.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to
start and exercise automatically. “See Weekly Exercise
Cycle.”
3.2.6 SYSTEM READY LED
The System Ready LED (green) has two main pro-
poses. First, the LED will be ON when the AUTO/
OFF/MANUAL switch is in the AUTO position, utility
is present, and there are no system alarms. This ON
state indicates the system is fully ready for automatic
operation.
Section 3 - Operation
Liquid-cooled 30 kW Generators