Section 7.1 - generator & speed control system, Troubleshooting reference chart – Generac Power Systems 941-2 User Manual
Page 109
Section 7.1
GENERATOR & SPEED CONTROL SYSTEM
PROBLEM
POSSIBLE CAUSE
REMEDY
PAGE
1. Engine starts, accelerates,
a. Carburetor linkage sticking with
a. Repair sticking throttle
3.4-3
shuts down at 4500 rpm
throttle stuck open.
b. Stepper Motor failed or seized.
b. Replace Stepper Motor.
3.6-1
c. Stepper Motor wire connections
c. Reconnect or repair.
3.6-1
broken or disconnected.
d. Stepper Motor not properly connected.
d. Reconnect wires.
3.6-1
2. Overvoltage condition and
a. Carburetor linkage sticking with
a. Repair sticking throttle.
3.4-3
speed control system cannot
throttle stuck partly open.
reduce output voltage.
b. Stepper Motor failed or seized.
b. Replace Stepper Motor.
3.6-1
c. Connection to Stepper Motor is
c. Repair or replace connections.
3.6-1
broken/disconnected with throttle open.
d. Stepper Motor not properly connected.
d. Reconnect Stepper Motor wires.
3.6-1
3. Engine speed is maintained
a. Carburetor linkage sticking with
a. Repair sticking throttle.
3.4-3
and no-load voltage is good.
throttle partly open.
However, when load is applied
b. Stepper Motor failed or seized.
b. Replace Stepper Motor.
3.6-1
output voltage drops.
c. Connection to Stepper Motor
c. Repair or replace connections.
3.6-1
Motor broken or disconnected.
d. Stepper Motor not properly
d. Reconnect Stepper Motor.
3.6-1
connected.
4. Engine does not accelerate
a. Carburetor linkage sticking
a. Repair sticking throttle.
3.4-3
when load is applied.
with throttle stuck closed.
b. Stepper Motor failed or seized.
b. Replace Stepper Motor.
3.6-1
c. Stepper Motor not properly
c. Reconnect Stepper Motor.
3.6-1
connected.
5. Engine speed and AC output
a. Stepper Motor failure.
a. Replace Stepper Motor.
3.6-1
voltage erratic under constant
b. Connection to Stepper Motor
b. Repair or replace connections.
3.6-1
load. AC output does not turn
broken or disconnected.
off intermittently.
c. Stepper Motor not properly
c. Reconnect Stepper Motor.
3.6-1
connected
6. Engine starts but Stepper
a. Stator Timing winding is open.
a. Repair/replace bad wire(s)
1.5-2
Motor does not move. Shut down
TIM1/TIM2 or replace Stator.
occurs after several seconds.
b. Timing winding in Stator shorted
b. Replace Stator.
1.5-2
to ground.
Page 7.1-1
TROUBLESHOOTING REFERENCE CHART