beautypg.com

13 torque specifications, 14 engine oil recommendations, 15 coolant recommendations – Generac Power Systems 004917-4 User Manual

Page 10: 16 before installation, 1 standby generator installation

background image

8

Generac

®

Power Systems, Inc.

NOTE:

Port 1 is for NG only and Port 2 is for LP vapor
only. No provision for dual fuel has been made.

Serious injury or damage may occur if not con-
figured properly. Please consult an authorized
Generac Service Dealer with any questions.

1.13 TORQUE SPECIFICATIONS

Cylinder Head ............................................15 (+ 90° + 90°) ft.lb.
Intake Manifold ................................................................13 ft.lb.
Exhaust Manifold..............................................................13 ft.lb.

1.14 ENGINE OIL RECOMMENDATIONS

The unit has been filled with 5W-20 engine oil at the
factory. Use a high-quality detergent oil classified “For
Service CC, SD, SE, SF.” Detergent oils keep the
engine cleaner and reduce carbon deposits. Use oil
having the following SAE viscosity rating, based on
the ambient temperature range anticipated before the
next oil change:

NOTE:

5W-30 full synthetic oil is highly recommended in
any element with temperatures above 90°F or
below 30°F.

Any attempt to crank or start the engine before
it has been properly serviced with the recom-
mended oil may result in an engine failure.

1.15 COOLANT RECOMMENDATIONS

Use a mixture of half low silicate ethylene glycol base
anti-freeze and half de-ionized water. Cooling system
capacity is about 12 U.S. quarts (11.4 liters). Use
only de-ionized water and only low silicate anti-
freeze. If desired, add a high quality rust inhibitor to
the recommended coolant mixture. When adding
coolant, always add the recommended 50-50 mix-
ture.

Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chromi-
umhydroxide (“green slime”) forms and will
cause overheating. Engines that have been
operated with a chromate base rust inhibitor
must be chemically cleaned before adding eth-
ylene glycol base anti-freeze. Using any high
silicate anti-freeze boosters or additives will
also cause overheating. It is also recommend
that any soluble oil inhibitor is NOT USED for
this equipment.

1.16 BEFORE INSTALLATION

Before installing this equipment, check the ratings of
both the generator and the transfer switch. Read
“Emergency Isolation Method” and “Total Circuit
Isolation Method” in Sections 2.5 and 2.6.

The generator’s rated wattage/amperage capacity
must be adequate to handle all electrical loads that
the unit will power. The critical (essential) loads may
need to be grouped together and wired into a sepa-
rate “emergency” distribution panel.

This generator can be installed in conjunction with
an engineered Generac “GTS” type transfer switch, if
necessary.

The standard transfer switch has no sensing or con-
trolling circuit boards. Instead, the generator control
console houses a “Printed Circuit Board Assembly”,
which controls all phases of operation, including
engine start up and load transfer.

2.1

STANDBY GENERATOR
INSTALLATION

Connecting this generator to an electrical sys-
tem normally supplied by an electric utility
shall be by means of a transfer switch, so as to
isolate the electric system from the utility distri-
bution system when the generator is operating.
Failure to isolate the electric system by these
means will result in damage to the generator
and may also result in injury or death to utility
workers due to backfeed of electrical energy.

If an open bottom is used, the engine-genera-
tor is to be installed over non-combustible
materials and should be located such that com-
bustible materials are not capable of accumu-
lating under the generator set.

DANGER

!

!

!

DANGER

Section 2 — Installation

QUIETSOURCE

Liquid-cooled 30 kW Generators

Temperature

Oil Grade (Recommended)

Above 80° F (27° C)

SAE 5W-20

32° to 80° F (-1° to 27° C)

SAE 5W-20

Below 32° F (0° C)

SAE 5W-20