OPERATING DATA

KW RATING (LP/NG)

30/30

ENGINE SIZE

1.5 Liter 4 cyl. inline

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

kW

AMP

CB Size

120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf

30
30
30

125
104

90

150
125
100

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load*

For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

Natural Gas

(ft

3

/hr.)

60

240
320
400
492

Propane

(gal/hr.)

ft

3

/hr

0.7

24

2.6

96

3.5

128

4.4

160

5.4

197

ENGINE COOLING

Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

System coolant capacity

US gal.

Heat rejection to coolant

BTU/hr.

Max. operating air temp. on radiator

°C (°F)

Max. ambient temperature

°C (°F)

1,800

2.0

135,000

60 (150)
50 (140)

COMBUSTION AIR REQUIREMENTS

Flow at rated power 60 Hz

cfm

72

SOUND EMISSIONS IN DBA

Exercising at 7 meters
Normal operation at 7 meters

59
73

EXHAUST

Exhaust flow at rated output 60 Hz

cfm

Exhaust temp. at muffler outlet

°F

237

1130

ENGINE PARAMETERS

Rated synchronous RPM

60 Hz

3600

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration

3% for every 10 °C above - °C

1.65% for every 10 °F above - °F

Altitude Deration

1% for every 100 m above - m

3% for every 1000 ft. above - ft.

25
77

183
600

* Refer to "Emissions Data Sheets" for maximum fuel flow for EPA and SCAQMD permitting purposes.

RATING:

All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a

reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
ISO-3046-1. Design and specifications are subject to change without notice.
KW rating is based on LPG Fuel and may derate with natural gas.