COMMERCIAL 80 kW

KW RATING

80

ENGINE SIZE

4.6 Liter V-8

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

KW

AMP

CB Size

120/240V, single phase, 1.0 pf

80 LP / 78 NG

333.3 LP / 325 NG

400

120/208V, 3-phase, 0.8 pf

80 LP / 78 NG

277.9 LP / 270.9 NG

300

120/240V, 3-phase, 0.8 pf

80 LP / 78 NG

240.8 LP / 234.8 NG

300

277/480V, 3-phase, 0.8 pf

80 LP / 78 NG

120.4 LP / 117.4 NG

150

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase

160

480V

3-phase

185

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Natural Gas

Propane

(ft3/hr.) (gal/hr.)

cu

ft/hr

Exercise

cycle

131

1.45

53

25% of rated load

312

3.45

126

50% of rated load

600

6.64

241

75% of rated load

835

9.25

336

100% of rated load

1154

12.78

465


ENGINE COOLING
Air

flow

(inlet air including alternator and combustion air)

ft3/min. 5,300

System coolant capacity

US gal.

4.0

Heat rejection to coolant

BTU/hr.

316,000

Max. operating air temp. on radiator

°C (°F)

60 (150)

Max. ambient temperature

°C (°F)

50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz

cfm

250


SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode

64

db(A) @ 23 feet at normal operating load

74


EXHAUST
Exhaust flow at rated output 60 Hz

m3/min. (cfm)

720

Exhaust temp. at muffler outlet

°F

840

ENGINE PARAMETERS
Rated synchronous RPM

60 Hz

3600

HP at rated KW

60 Hz

130

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature

Deration

3% for every 10 °C above - °C

25

1.65% for every 10 °F above - °F

77

Altitude

Deration

1% for every 100 m above - m

183

3% for every 1000 ft. above - ft.

600

OPERATING DATA

COMMERCIAL 80 kW

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power
and condition, etc.