Operating data – Generac Power Systems SG020 User Manual
Page 3
STANDBY
SG020
SG025
GENERATOR OUTPUT VOLTAGE/KW-60Hz
NG/LP
Rated AMP
NG/LP
Rated AMP
120/240V, 1-phase, 1.0 pf
20
83.3
25
104.2
120/208V, 3-phase, 0.8 pf
20
69.5
25
86.8
120/240V, 3-phase, 0.8 pf
20
60.2
25
75.3
277/480V, 3-phase, 0.8 pf
20
30.1
25
37.6
MOTOR STARTING KVA
Maximum at 35% instantaneous voltage dip
with standard alternator; 60 hz
40
46
FUEL
Fuel consumption—60 hz—100% Load
N.G.
L.P.
N.G.
L.P.
ft.
3
/hr.
369
153
442
183
m
3
/hr.
10.4
4.3
12.5
5.2
COOLING
Coolant capacity
System lit.(US gal.)
6.6 (2)
6.6 (2)
Engine lit.(US gal.)
0.9 (0.25)
0.9 (0.25)
Radiator lit.(US gal.)
6.6 (1.75)
6.6 (1.75)
Coolant flow/min.
60 hz lit.(US gal.)
40 (10.6)
40 (10.6)
heat rejection to coolant
60 hz BTU/hr.
96,000
120,000
Cooling air flow
60 hz m
3
/min. (cfm)
45 (1590)
45 (1590)
COMBUSTION AIR REQUIREMENTS
Flow at rated power
60 hz m
3
/min. (cfm)
1.8 (65)
2.3 (81)
EXHAUST
Exhaust flow at rated output
60 hz m
3
/min. (cfm)
6.0 (212)
7.3 (260)
Max. recommended back pressure
Kpa (hg)
5.0 (1.5")
5.0 (1.5")
Exhaust temp. at rated output
o
C (
o
F)
593 (1100)
635 (1175)
Exhaust outlet size
N.P.T. (female)
1.5"
1.5"
ENGINE
Rated RPM
60 hz
3600
3600
hP at rated KW
60 hz
30
37
Piston speed
60 hz m/min. (ft./min.)
590 (1937)
590 (1937)
BMEP (psi)
60 hz - psi
78
97
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature
-3% for every 10
o
C above - °C
40
25
-1.5% for every 10
o
F above - °F
104
77
Altitude
-3% for every 300 m above - m
913
150
-3% for every 1000 ft. above - ft.
3000
500
OPERATING DATA
SG020 / SG025