beautypg.com

2 generator location, 3 generator mounting and support, 4 basic standby electric system – Guardian Technologies 004992-2 User Manual

Page 11

background image

9

After the system has been installed, do nothing
that might render the installation in noncompli-
ance with such codes, standards and regula-
tions.

2.1.1 NFPA STANDARDS

The following published standards booklets pertain-
ing to standby electric systems are available form the
National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269:

NOTE:

It is essential to use the latest version of any stan-
dard to ensure correct and current information.

• NFPA No. 37, STATIONARY COMBUSTION

ENGINES AND GAS TURBINES.

• NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-

TEMS FOR HEALTH CARE FACILITIES.

• NFPA No. 220, STANDARD TYPES OF BUILDING

CONSTRUCTION

• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
• NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE

LIQUIDS CODE.

• NFPA No. 10, INSTALLATION, MAINTENANCE AND

USE OF PORTABLE FIRE EXTINGUISHERS.

2.1.2 OTHER PUBLISHED STANDARDS

In addition to NFPA standards, the following infor-
mation pertaining to the installation and use of
standby electric systems is available:

NOTE:

It is essential to use the latest version of any stan-
dard to ensure correct and current information.

• Article X, NATIONAL BUILDING CODE, available

from the American Insurance Association, 85 John
Street, New York, N.Y. 10038.

• AGRICULTURAL WIRING HANDBOOK, obtainable

from the Food and Energy Council, 909 University
Avenue, Columbia, MO, 65201.

• ASAE EP-364.2, INSTALLATION AND MAINTE-

NANCE OF FARM STANDBY ELECTRIC POWER,
available from the American Society of Agricultural
Engineers, 2950 Niles Road, St. Joseph, MI 49085.

• A52.1, AMERICAN NATIONAL STANDARD FOR

CHIMNEYS, FIREPLACES AND VENTING SYS-
TEMS, available from the American National
Standard Institute, 1430 Broadway, New York, N.Y.
10018.

2.2

GENERATOR LOCATION

Install the generator set, in its protective enclosure
outdoors, where adequate cooling and ventilating air
always is available. Consider these factors:

• Install the unit where air inlet and outlet openings

will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drift-
ing, consider using a windbreak to protect the unit.

• Install the generator on high ground where water

levels will not rise and endanger it.

• This genset must be installed on a level surface.

The base frame must be level within 1/2 inch all
around.

• Allow sufficient room on all sides of the generator

for maintenance and servicing. A good rule is to
allow five feet of space on all sides.

• Where strong prevailing winds blow from one

direction, face the generator air inlet openings into
the prevailing winds.

• Install the generator as close as possible to the

transfer switch. This reduces the length of wiring
and conduit.

• Install the generator as close as possible to the fuel

supply, to reduce the length of piping. HOWEVER,
REMEMBER THAT LAWS OR CODES MAY REG-
ULATE THE DISTANCE.

2.3

GENERATOR MOUNTING AND
SUPPORT

Retain the generator compartment to a concrete slab
with 1/4-inch masonry type anchor bolts. Be sure the
bolts are long enough to retain the compartment. The
slab should be at least six inches thick and should
extend beyond the enclosure to a distance of at least
three inches on all sides. See Section 6 for generator
major dimensions.

2.4

BASIC STANDBY ELECTRIC
SYSTEM

Figure 2.1 (on page 10) shows a schematic diagram
of a basic standby electric system. Both the UTILITY
power supply and the STANDBY (GENERATOR) out-
put are connected to an approved transfer switch.
The transfer switch is required by electrical code and
serves the following functions:

• Allows the LOAD circuits to be connected to only

one power supply at a time.

• Prevents electrical backfeed between the generator

and the UTILITY power circuits.

Notice that both the STANDBY and the UTILITY
power supplies to the transfer switch are protected
against overload by a main line circuit breaker.

‹

‹

!

Section 2 — Installation

40kW Liquid-cooled Generators