SPECIFICATIONS

GENERATOR

Type ............................................................................. Synchronous
Rotor Insulation ....................................................................Class F
Stator Insulation ...................................................................Class F
Total Harmonic Distortion .........................................................< 5%
Alternator Output Leads 3-phase ........................................... 4-wire
Bearings .........................................................................Sealed Ball
Coupling .......................................................................Flexible Disc
Load Capacity (Standby Rating) ............................................20kW*
*

NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349,

ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural

gas.

Excitation System ....................................................................Direct
Generator Output Voltage/kW - 60 Hz

kW

Amp CB Size

120/240V, 1-phase, 1.0 pf

20

83

100

120/208V, 3-phase, 0.8 pf

20

69

80

Generator Locked Rotor KVA Available @ Voltage Dip of 35%
Single-phase or 208 3-phase ............................................. 30 KVA

ENGINE

Make ................................................................................... Generac
Model ..................................................................................... In Line
Cylinders and Arrangement ............................................................ 4
Displacement ....................................................................... 1.6 Liter
Bore ...................................................................................... 3.15 in.
Stroke ................................................................................... 3.13 in.
Compression Ratio .............................................................9.75-to-1
Air Intake System ...............................................Naturally Aspirated
Valve Seats ................................................................... Replaceable
Lifter Type .......................................................................... Hydraulic

Engine Parameters
Rated Synchronous RPM ..............................................60 Hz, 3600
HP at rated kW ....................................................................... 35 HP

Exhaust System
Exhaust Flow at Rated Output 60 Hz .................................. 177 cfm
Exhaust Temperature at Rated Output .................................. 910° F

Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz ................................................... 80 cfm

Governor
Type .................................................................................. Electronic
Frequency Regulation ...................................................Isochronous
Steady State Regulation ........................................................± .25%
Adjustments:
Speed ............................................................................ Selectable

‹

‹

Engine Lubrication System
Type of Oil Pump ...................................................................... Gear
Oil Filter .............................................................Full Flow, Cartridge
Crankcase Oil Capacity ....................................................4 U.S. qts.

COOLING SYSTEM

Type ....................................................................................... Closed
Water Pump .................................................................... Belt Driven
Fan Speed ................................................................................ 2550
Fan Diameter .....................................................................16 inches
Fan Mode ..............................................................................Pusher
Air Flow (inlet air including alternator and
combustion air) .......................................................... 1528 ft3/min.
Coolant Capacity ...........................................................2.0 U.S. gal.
Heat Rejection to Coolant ..........................................107,000 Btu/h
Maximum Operating Air Temp. on Radiator ..............60° C (150° F)
Maximum Ambient Temperature ................................50° C (140° F)

FUEL SYSTEM

Type of Fuel ......................................... Natural Gas, Propane Vapor
Carburetor ...................................................................... Down Draft
Secondary Fuel Regulator .................................................Standard
Fuel Shut-off Solenoid ........................................................Standard
Operating Fuel Pressure ...................... 5 in. - 14 in. Water Column

Fuel Consumption - ft

3

/hr (Natural Gas/LPV)

Exercise

25%

50%

75%

100%

Cycle

Load

Load

Load Load

59/23 124/49 188/75 250/99 315/125

ELECTRICAL SYSTEM

Battery Charge Alternator ............................................12V, 15 Amp
Static Battery Charger ............................................................2 Amp
Recommended Battery ...................................... Group 26, 525CCA
System Voltage .....................................................................12 Volts

Voltage Regulator
Type .................................................................................. Electronic
Sensing ........................................................................ Single-phase
Regulation ................................................................................± 1%
Features ................................................. V/F Adjustable, Adjustable

Voltage and Gain LED Indicators

Power Adjustment for Ambient Conditions
Temperature Deration
3% for every 10° C above °C ..................................................... 40
1.65% for every 10° above °F .................................................. 104
Altitude Deration
1% for every 100 m above m ................................................... 914
3% for every 1000 ft. above ft. ............................................... 3000

Controller .................................................R-200

‹

‹

‹

6-1

Standby Generator Sets

Specifications

GenSpec030 Rev.

0 05/06