Product specs, Pecifications – Goodman Mfg GPG13M User Manual
Page 3

2
www.goodmanmfg.com
SS-GPG13MC
SS-GPG13MC
www.goodmanmfg.com
3
P
roduct
S
PecificationS
P
roduct
S
PecificationS
s
PeCifiCaTions
GPG1336
090M43A*
GPG1348
090M43A*
GPG1360
090M43A*
Cooling Capacity
Total BTU/h
36,000
46,000
56,500
Sensible BTU/h
27,800
36,700
43,800
SEER / EER
13.0 / 11.0
13.0 / 11.0
13.0 / 10.6
Decibels
78
80
80
AHRI #s
4385095
4385098
4385100
Heating Capacity
Input BTU/h
92,000
92,000
92,000
Output BTU/h
73,600
73,600
73,600
AFUE
80
80
80
Temperature Rise Range
45 - 75
45 - 75
45 - 75
No. of Burners
4
4
4
Orifice Size (Natural/Propane)
43/ 55
43/ 55
43 / 55
Evaporator Motor / Coil
Type
DD
X-13
X-13
Wheel (D x W)
10” x 9”
11” x 10”
11” x 10”
Indoor Nominal CFM
1,200
1,550
1,750
Motor Speed Tap (Cooling)
low
T4
T4
RPM/Amps (Cooling)
910/3.06
1050/5.8
1,050/7.4
Horsepower
⅓
¾”
1.0
Face Area (ft²)
5.67
5.67
5.67
Rows Deep/ Fins per Inch
4/ 14
4/ 14
4/ 14
Piston Size (Cooling)
0.068
0.076
0.087
Filter Size (ft²)
4.2
5.1
6.3
Drain Size (NPT)
¾”
¾”
¾”
Refrigerant Charge (oz.)
110
125
185
Condenser Fan
Horsepower - RPM
¼ - 830
¼ - 1,075
¼ - 1,100
Fan Diameter/ # of Fan Blades
22” / 3
22” / 3
22” / 3
Outdoor Nominal CFM
3,500
3,500
3,250
Coil
Face Area (ft²)
15.4
15.4
15.4
Rows Deep/ Fins per Inch
1/ 24
1/ 24
1/ 24
Compressor
Quantity / Type
1 / Scroll
1 / Scroll
1 / Scroll
Stage
Single
Single
Single
Compressor RLA/LRA
10.4/73.0
13.1/83.1
16.0/ 134
Electrical Data
Voltage-Phase-Frequency
208/230-3-60
208/230-3-60
208/230-3-60
Indoor Blower FLA/ LRA
3.06/ 4.1
5.8
7.4
Outdoor Fan RLA/ LRA
1.5 / 3.0
1.4/ 2.9
1.4/ 2.9
Total Unit Amps
15
20.3
24.8
Min. Circuit Ampacity
17.6
23.6
29
Max. Overcurrent Protection
25 amps
35 amps
45 amps
Entrance Size Power Supply
1⅛”
1⅛”
1⅛”
Entrance Size Control Voltage
⅞”
⅞”
⅞”
Operating Weight (lbs)
490
523
533
Ship Weight (lbs)
513
545
555
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² Must use time-delay fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.