KW RATING
60
ENGINE SIZE
3.0 Liter V-6
GENERATOR OUTPUT VOLTAGE/KW - 60Hz
KW
AMP
CB Size
120/240V, single phase, 1.0 pf
60
250
300
120/208V, 3-phase, 0.8 pf
60
208.4
250
120/240V, 3-phase, 0.8 pf
60
180.6
200
277/480V, 3-phase, 0.8 pf
60
90.3
100
GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%
Single phase or 208V & 240V 3-phase
120
480V
3-phase
141
ENGINE FUEL CONSUMPTION
(Natural Gas) (Propane)
Natural Gas
Propane
(ft
3
/hr.) (gal/hr.)
cu
ft/hr
Exercise
cycle
123
1.34
48.7
25% of rated load
260
2.84
103.3
50% of rated load
500
5.46
198.6
75% of rated load
700
7.64
277.9
100% of rated load
960
10.48
381.3
ENGINE COOLING
Air
flow
(inlet air including alternator and combustion air)
ft
3
/min. 3,280
System coolant capacity
US gal.
2.5
Heat rejection to coolant
BTU/hr.
270,000
Max. operating air temp. on radiator
°C (°F)
60 (150)
Max. ambient temperature
°C (°F)
50 (140)
COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz
cfm
180
SOUND EMISSIONS IN DBA
db(A) @ 23 feet in exercise mode
63
db(A) @ 23 feet at normal operating load
71
EXHAUST
Exhaust flow at rated output 60 Hz
cfm 494
Exhaust temp. at muffler outlet
°F
1,050
ENGINE PARAMETERS
Rated synchronous RPM
60 Hz
3600
HP at rated KW
60 Hz
94
POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature
Deration
3% for every 10 °C above - °C
25
1.65% for every 10 °F above - °F
77
Altitude
Deration
1% for every 100 m above - m
183
3% for every 1000 ft. above - ft.
600
OPERATING DATA
COMMERCIAL 60 kW
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance
with ISO-3046-1. Design and specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient
temperature, altitude, engine power and condition, etc.
COMMERCIAL SERIES