FieldServer FS-8700-47 User Manual
Page 47

FS-8700-47 DNP 3.0 Driver Manual
Page 47 of 51
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]
Error Message
Explanation
DNP:#20 FYI. Node Indicates that 
Event Buffers Have Overflowed. 
This message is for information only. It is printed when a remote 
device reports that its event buffers have overflowed. 
DNP:#21 FYI. Length=%d invalid. 
Setting to %d. 
DNP:#23 FYI. Store rqsted but no 
Data. 
A poll for data contained a response with no data. This can be 
valid, e.g. you request Change Data and there isn’t any. 
DNP:#25 FYI. Slave Cant use 
Qual=6. for Md=<%s> 
You cannot use a qualifier of 6 when configuring a Server. See 
Appendix A.11 for a list of valid qualifiers.
7
DNP:#27 Err. Slave: Too many 
bytes=%s 
to
send.
Reduce
message length
Change the Map Descriptor length so that the message contains 
fewer data bytes. 
7
DNP:#29 Err. Cant process this 
qualifier (%d) 
The driver does not support this qualifier when processing response 
from a remote DNP device. Configure the device to use a different 
qualifier.
7
DNP:#30 FYI. Data to store but 
no mapDesc found. 
A message has been received from a remote DNP device but the 
driver has not been configured to store this data. 
DNP:#31 Resp. data contained 
obj=%d vari=%d. MD rqd for 
storage. 
Some responses (Class Data) contain multiple data types. The 
driver could not find a Map Descriptor to store some of the data. 
Refer to Section 4.4.7 to correct the problem. 
7
DNP:#32 Err. Cant store for index 
style %d 
The driver can only store data from messages where the data 
elements are indexed in a supported style. Take a log and send 
with your configuration file to FST Tech Support. 
DNP:#33 Err. Qty items + array 
offset > end array. md=<%s> 
Cant store all. qty/max= %d/%d 
You need to make the data array longer (and/or the length of the 
Map Descriptor.)
7
DNP:#35 Err. Relay
Output.
Status data array too short. 
DNP:#36 Err. Relay Output. 
Status data array too short. 
The Data Array designated with e DA_Byte_Name parameter in the 
CSV file is too short. 
7
DNP:#37 Err. Relay Output. 
Bridge cant implement action 
code 
The driver only supports ‘Latch On’ and ‘Latch Off’ and Relay 
output actions. Reconfigure the remote device to use a different 
relay action. 
DNP:#38 Err. Storage Method 
Unknown. (%d) 
Take a log and send the log and configuration file to FST Tech 
Support. 
DNP:#40 Err. Abandoned data 
store. Too many data object 
types. 
The DNP 3.0 driver can process a max of 20 different data objects 
when storing class data. Reconfigure the remote device for fewer 
data objects in the class requested. 
DNP:#41 Err. MD=
short. Rqd=%d 
DNP:#41 Err. MD=
too short. Rqd=%d 
8
DNP:#42 FYI. You could have 
used a MD called 
expose diagnostic info. 
DNP:#42 FYI. You could have 
used a MD called 
expose diagnostic info. 
Error! Reference source not found. and 0 contain additional 
information. 
DNP:#43a Err. Diagnostic #3. Call 
Support. 
If any variation of MSG #43 is printed, take a log and call Tech 
support. 
DNP3:#44 FYI. Link Reset 
Suppressed. Port=%d 
The configuration file has suppressed the requirement for link reset. 
If this corresponds to your expectation then you can safely ignore 
this message, If not, see Appendix A.15 
7
Edit the CSV file, download to the FieldServer and reset the FieldServer.