beautypg.com

FieldServer Profibus DP FS-8700-20 User Manual

Page 16

background image

FS-8700-20 Profibus DP Driver Manual

Page 16 of 22

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldServer.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

Appendix A. Special Driver Parameters

Appendix A.1. DP_Buffer

Within the Profibus DP card, the FieldServer can access data from two distinct buffers. The
Input buffer is the data that is sent from the slave to master. The Output buffer is the data
sent from the master to the slave. Each Map Descriptor specifies which one of these buffers
to access in the card.

DP_Buffer

Description

Input

Data to the master from a slave

Output

Data from the master to a slave

Appendix A.2. Data_Type, Address & Length

Each Map Descriptor also specifies the Profibus DP data type. The data arrives from a
Slave or is sent from a Master as a sequence of bytes. By specifying the DP data type, the
driver knows how to interpret the bytes within the buffer. The supported types are Bit, Byte,
Word and Float. To indicate where in the buffer to access the data, the Address field is
used. For Byte, Word and Float type mappings, the address specifies the offset in bytes
from the beginning of the buffer. For Bit type mappings, the address specifies the offset in
bits from the beginning of the buffer. A bit offset of 0 would access the least significant bit in
the first byte in the designated buffer.

Data_Type

Description

Bit

Transfer Length bits to Data Array

Byte

Transfer Length bytes to Data Array

Word

Swap the bytes and transfer Length words to Data Array

Float

Swap the bytes and transfer Length floats to Data Array