FieldServer Safetran FS-8700-128 User Manual
Page 7
![background image](/manuals/103780/7/background.png)
FS-8700-128 Safetran SCS-128 Manual
Page 7 of 15
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: [email protected]
4.2.
Client Side Connection Descriptions
Section Title
Connections
Column Title
Function
Legal Values
Port
Specify which port the device is connected
to the FieldServer
P1-P8
1
Protocol
Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Baud*
Specify baud rate
75, 150, 300 ,600, 1200, 2400, 9600
(Vendor limitation)
Parity*
Specify parity
Even (Vendor limitation)
Data_Bits*
Specify data bits
8 (Vendor limitation)
Stop_Bits*
Specify stop bits
1 (Vendor limitation)
Handshaking* Specify hardware handshaking
None
Poll_Delay*
Time between internal polls
0-32000 seconds, 0.05 seconds
Example
//
Client Side Connections
Connections
Port,
Protocol,
Baud,
Parity,
Handshaking,
Poll_Delay
P8,
SCS-128,
9600,
Even,
None,
0.100s
4.3.
Client Side Node Descriptors
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric
characters
Node_ID
SCS-128 station address of physical Server Node
1-127
Protocol
Specify protocol used
SCS-128
SCS128
Safetran SCS-128
Connection
Specify which port the device is connected to the
FieldServer
P1-P8
1
SCS128_Ack*
If ON, Ack will be sent to Server upon receipt of every
indication response
OFF, ON
Example
// Client Side Nodes
Nodes
Node_Name,
Node_ID,
Protocol,
Connection,
SCS128_Ack
NODE_A,
1,
SCS-128,
P8,
OFF
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.