beautypg.com

Friedrich CP14-18-24 CP24N30 User Manual

Page 14

background image

14

Problem

Possible Cause

Action

Unit does not run

Fuse blown or circuit tripped

Replace fuse, reset breaker. If repeats, check fuse
or breaker size. Check for shorts in unit wiring &
components

Power cord not plugged in

Plug it in

System switch in "OFF" position

Set switch correctly

Inoperative system switch

Test for continuity in each switch position

Loose or disconnected wiring at switch or other
components

Check wiring & connections. Reconnect per wiring
diagram

Problem

Possible Cause

Action

Evaporator coil

freezes up

Dirty fi lter

Clean as recommended in Owner's Manual

Restricted airfl ow

Check for dirty or obstructed coil. Use pressure
wash or biodegradable cleaning agent to clean

Inoperative t-stat

Test for shorted t-stat or stuck contacts

Short of refrigerant

De-ice coil & check for leak

Inoperative fan motor

Test fan motor & replace if inoperative

Partially restricted capillary tube

De-ice coil. Check temp. differential (delta T) across
coil. Touch test coil return bends for same temp.
Test for low running current

Problem

Possible Cause

Action

Compressor runs

continually & does not

cycle off

Excessive heat load

Unit undersized. Test cooling performance & replace
with larger unit if needed

Restriction in line

Check for partially iced coil & check temperature
split across coil

Refrigerant leak

Check for oil at silver soldered connections. Check
for partially iced coil. Check split across coil. Check
for low running amperage

T-stat contacts stuck

Check operation of t-stat. Replace if contacts
remain closed.

T-stat incorrectly wired

Refer to appropriate wiring diagram

Problem

Possible Cause

Action

T-stat does not turn

unit off

T-stat contacts stuck

Disconnect power to unit. Remove cover of t-stat &
check if contacts are stuck. If so, replace t-stat

T-stat set at coldest point

Turn to higher temp. setting to see if unit cycles off

Incorrect wiring

Refer to appropriate wiring diagrams

Unit undersized for area to be cooled

Refer to industry standard sizing chart

Cooling Only Room Air Conditioners: Troubleshooting Tips

This manual is related to the following products: