Ed series, Uvs plus, Model -a – Falcon ED3000-A User Manual
Page 16

ED Series
TM
UVS PLUS
®
Model -A
ED Series Model -A Frequency Converter (120V Input/Output)
Model Number
ED-1000-A
ED-1500-A
ED-2000-A
ED-3000-A
ED-4000-A
Nominal VA
1000
1500
2000
3000
4000
Electrical Input
AC Voltage, +10% -20%
120V
120V
120V
120V
120V
Current-Amps
10.4
15.6
20.8
29
39
Frequency Range
47 – 450
47 - 450
47 - 450
47 - 450
47 - 450
Electrical Output
AC Voltage, ± 3%
120V
120V
120V
120V
120V
Watts @ 50 or 60 Hz
700
1050
1400
2100
2800
Watts @ 400 Hz (-400 option)
595
892
1190
1785
2380
Current-Amps @ 50/60 Hz
8.3
12.5
16.7
25
33
Current-Amps @ 400Hz
7.1
10.6
14.2
21.3
28
50/60 Hz Non – Linear
Repetitive Peak (Amps)
20
30
40
60
80
400 Hz Non – Linear
Repetitive Peak (Amps)
14.2
21.3
28.3
42.5
56
Total Harmonic Distortion
< 3% @ 100% Linear Load, < 5% @ 100% Non – Linear Load
Overload
200% for 0.5 Seconds, 120% for 30 Seconds
Dynamic Response
± 5% RMS for 100% Step Load Change, 1ms Recovery Time
Output Protection
Short Circuit and Overload
Electrical Connections
Input
6’ Cord with
5-15P
8’ Cord with
5-20P
8’ Cord with
L5-30P
Hardwired
Hardwired
Output
(4) 5-15R
(4) 5-15R
(4) 5-15R
Hardwired
Hardwired
Environmental
Operating Temperature
0º C to 35º C (32º F to 95º F)
Humidity
10% to 95% Non – Condensing
Altitude
7,000 Feet
Cooling
Low Velocity Forced Air Fans
Audible Noise @ 1.5 Meters
49dBA
54dBA
Controls and Indicators
Sequenced LEDs
Load Level
Single LED
Utility Present, Summary Alarm, Inverter On
Audible Alarms
Utility Interrupt, Inverter Failure, Overload
Communications
Dry Contact Closures on Utility Loss via 9 Pin “D” Connector
Mechanical
Dimensions H x W x D inches (mm)
13.5 x 6.25 x 19.4 (342.9 x 158.8 x 492.8)
Weight lb. (kg)
25 (11.3)
38 (17.2)
38 (17.2)
50 (22.7)
50 (22.7)
Specify input/output frequency, 50/60 or 400Hz (any combination).
Standard models shown. Custom configurations available; Consult Factory.
Note: For ED3000-A and ED4000-A models add a -400 to the end of the model number for a
400Hzoutput