Friedrich CP05C10 User Manual
Page 17
—17—
COMPLAINT
CAUSE
REMEDY
Fan motor noise.
Fan blade
If cracked, out of balance, or partially missing,
replace it.
Blower wheel If cracked, out of balance, or partially missing,
replace it.
Loose set screw
Tighten it.
Worn bearings
If knocking sounds continue when running
replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
Compressor will not run,
Voltage
Check voltage. See the limits on the preceding
fan motor runs.
page. If not within limits, call an electrician.
Wiring
Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon-
nected, refer to wiring diagram for identification,
and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct
the connections.
Thermistor
Check the TEMP control. If not at the lowest
number, set TEMP control to this setting.
Check the continuity of the thermistor. Replace
the control board if the circuit is open.
Capacitor (discharge
Check the capacitor.
capacitor before
Replace if not within ±10% of manufacturer’s
servicing.)
rating, replace if shorted, open, or damaged.
Compressor
Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor.
Overload
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)
Compressor cycles on
Voltage
Check the voltage. See the limits on the
overload.
preceding page. If voltage is not within these limits,
call an electrician.
Overload
Check overload, if externally mounted.
Replace if open. (If the compressor temperature
is high, remove the overload, cool, and retest.)