Appendix d - system wiring guides, Wiring guide for subidr-8, Channel 1 of 3 – Honeywell SUB Series Interval Data Recorders 62-0342-01 User Manual
Page 8: Sub series interval data recorders, Fig. 12. wiring overview for subidr-8, Idr a idr z

SUB SERIES INTERVAL DATA RECORDERS
62-0342—01
8
APPENDIX D - SYSTEM WIRING GUIDES
Fig. 12. Wiring overview for SUBIDR-8.
Note: Meter 1 must be installed within
100 feet of IDR. Meters 2-8 must be installed
within 500 feet of IDR.
(Up to 8 Meters)
(One of three channels shown for clarity.)
(Up to 8 Meters)
~
~
Channel 1 of 3
4-Conductor
Flat Modular Cable
Up to 4000 Feet Total
Daisy-Chain or
Star Connection
Up to 52 SUBIDR-8s per channel
AC Adapter
SUB-RS232K
6' cable provided by
Honeywell
(15 ft max.)
8-conductor cable
& modular plug
DB-9 (DTE) Connector
PC
RJ-45
RJ-11
8-Cond.
RJ-45
RJ-11
6-Cond.
RJ-45
6-Cond.
RJ-45
Wiring Guide for SUBIDR-8
IDR A
IDR Z
CONNECTION CABLE
TYPE CONNECTOR
SUBIDR to Honeywell Meter #1
8-cond. 22-26 AWG
RJ-45
flat
modular
cable
SUBIDR to Honeywell Meters #2-8
6-cond. 22-26 AWG
RJ-45
(Pins 1 & 8 not used)
SUBIDR to SUBIDR
4-cond. 26 AWG
RJ-11
SUBIDR to SUB-RS232K
4-cond. 26 AWG
RJ-11
SUB-RS232K to Computer *
8-cond. 22-26 AWG
RJ-45/DTE
flat
modular
cable
SUB-RS232K to Modem *
8-cond. 22-26 AWG
RJ-45
flat
modular
cable
SUBIDR to SUB-USBK *
Allows connection directly
to
the
computer
USB
SUBIDR to Pulse Meter
2-cond. 14-22 AWG
* Supplied by Honeywell
Note: When constructing field-installed cables, modular cables must be made
so that the individual wires go through on the same pin number.