Routine Maintenance

It is not normally necessary to open the refrigerant circuit. If a problem is suspected it is strongly recommended
that unit maintenance or repair is undertaken by a CITY & GUILDS 2078 (or equivalent) COMPETENT
REFRIGERATION ENGINEER. A City and Guilds 2078 (or equivalent) certificate will soon be mandatory.

Daily

 Check that the "ON / OFF" switch/isolator is in the "ON" or " I " position.
 Check condenser fan for airflow.

Weekly

 Check condensate drain operation.

Monthly

 Check condenser fins and grilles for cleanliness or damage. Repair as necessary.

 Check condenser fan blades for damage.

Quarterly

 Check tightness of electrical connections.

 Check all wiring for damage to insulation.

 Check running current.

 Clean condensate line strainer.

Bi-annually

 Check operation of refrigerant circuit (including temperatures and pressures)

 Check the pipework connections for

Annually

 Thoroughly clean unit including condenser fins.

 Check internal pipework and components for signs of wear or damage.

Note:

 Some safety cut outs are auto reset, and unless isolated from the mains the unit can be re-started without

warning.

 Pressure switches should be adjusted with the power off.

 Any work done to the Compressed Air Dryer involving entry into the control panel, fitting gauges, adjusting

controls, charging the system, evacuating the system or opening the system in any way, must be carried out
by a FULLY QUALIFIED REFRIGERATION ENGINEER.