SD and SK SLC Device Installation

151209

5-5

Figure 5-1 and Figure 5-2 show how wire length is determined for out-and-back tap
and T-tap style wiring.

Figure 5-1 Calculating wire run length for a simple out and back tap

When using T-taps, the total length of all taps and the main bus must not exceed
40,000 feet. This requirement must be met in addition to the maximum distance
requirements for the various wire gauges.

Figure 5-2 Calculating Wire Run Length for a T-tap

Pages: 1 … 93 94 95 96 97 … 244
  • wrong Brand
  • wrong Model
  • non readable
See also other documents in the category Honeywell Safety:
  • VISTA-20P (80 pages)
  • GEC (3 pages)
  • VISTA-250BP (80 pages)
  • VISTA-128BP (80 pages)
  • ADEMCO LYNXR Series (72 pages)
  • NOTIFIER IFS-2600 (80 pages)
  • GALAXY 16103 (18 pages)
  • HD70 (1 page)
  • HMR4007 (8 pages)
  • INTELLIGUARD 9000 (8 pages)
  • HCD545X (2 pages)
  • RAPID EYE K9696V2 (96 pages)
  • MS-10UD (1 page)
  • RCA902N (80 pages)
  • TRADELINE C554A (4 pages)
  • EXCEL ADT-HRSI (4 pages)
  • EKZ008200B (97 pages)
  • SYSTEM OVERVIEW N7003V3 (56 pages)
  • WSK-24 (16 pages)
  • DUCT-MOUNT AND OUTDOOR-MOUNT H7655B (8 pages)
  • ADEMCO VISTA VISTA-15P (64 pages)
  • MK VIII (326 pages)
  • Galaxy 16 (30 pages)
  • Smoke Alarm (15 pages)
  • HB73 (1 page)
  • EQUIPMENT MONITORING SYSTEM W8710A (8 pages)
  • 2077D (17 pages)
  • MS-9200UDLSE (228 pages)
  • Photoelectronic Smoke/Temperature Detector 5808W3 (4 pages)
  • XL 800 SERIES (36 pages)
  • 800-04433V1 (16 pages)
  • XG1000 (4 pages)
Home Brands Popular manuals Recently added
Manuals Directory

© 2012–2025, azmanual.top
All rights reserved.